SMA Modbus register address

Name

SMA Modbus access

Unit ID

SMA Modbus data type

SMA Modbus data format

Resolution

Group

Channel

Value range / unit / set values

Default value

30001

SMA Modbus profile revision

RO

1

U32

RAW

1

Type Label

SMA Modbus profile revision

-

-

30003

SUSyID

RO

1

U32

RAW

1

Type Label

Parameter.Nameplate.SusyId

481

481

30005

Serial number

RO

1

U32

RAW

1

Type Label

Parameter.Nameplate.SerNum

-

-

30007

Modbus data change count

RO

1

U32

RAW

1

Type Label

Modbus data change count

-

-

30051

Device class

RO

3

U32

TAGLIST

-

Type Label

Parameter.Nameplate.MainModel

8007: Battery Inverter

8007: Battery Inverter

30053

Device type

RO

3

U32

TAGLIST

-

Type Label

Parameter.Nameplate.Model

19017: Sunny Island 50
19018: Sunny Island 30
19019: Sunny Island 60 US480
19020: Sunny Island 40 US480
19021: Sunny Island 27 US208

19035: Sunny Tripower Storage 50

30055

Manufacturer

RO

3

U32

TAGLIST

-

Type Label

Parameter.Nameplate.Vendor

461: SMA

461: SMA

30057

Serial number

RO

3

U32

RAW

1

Type Label

Parameter.Nameplate.SerNum

-

-

30059

Firmware version

RO

3

U32

FW_VERSION

1

Type Label

Parameter.Nameplate.PkgRev

-

3.04.80.R

30193

UTC system time

RO

3

U32

DATE_TIME

1

LriGrpNameplate

UTC system time

-

-

30197

Current event number

RO

3

U32

FIX0

1

Status

Operation.Evt.EvtNoShrt

-

-

30199

Waiting time until feed-in

RO

3

U32

DURATION

1

Status

Operation.RmgTms

s

-

30201

Condition

RO

2 / 3

U32

TAGLIST

-

Status

Measurement.Operation.Health

35: Fault
303: Off
307: Ok
455: Warning

307: Ok

30203

Nominal power in Ok Mode

RO

3

U32

FIX0

1

Status

Measurement.Operation.HealthStt.Ok

W

-

30205

Nominal power in Warning Mode

RO

3

U32

FIX0

1

Status

Measurement.Operation.HealthStt.Wrn

W

-

30207

Nominal power in Fault Mode

RO

3

U32

FIX0

1

Status

Measurement.Operation.HealthStt.Alm

W

-

30211

Recommended action

RO

3

U32

TAGLIST

-

Status

Operation.Evt.Prio

-

-

30213

Message

RO

3

U32

TAGLIST

-

Status

Measurement.Operation.Evt.Msg

302: -------

302: -------

30215

Fault correction measure

RO

3

U32

TAGLIST

-

Status

Measurement.Operation.Evt.Dsc

302: -------

302: -------

30217

Grid relay/contactor

RO

3

U32

TAGLIST

-

Status

Measurement.Operation.GriSwStt

51: Closed
311: Open

311: Open

30219

Reason for derating

RO

3

U32

TAGLIST

-

Status

Measurement.Operation.DrtStt

884: not active

302: -------

30225

Insulation resistance

RO

3

U32

FIX0

1

DC Side

Measurement.Isolation.LeakRis

Ohm

-

30227

Key switch

RO

3

U32

TAGLIST

-

Status

Operation.KeySwStt

-

-

30229

Local time

RO

3

U32

DATE_TIME

1

Device

DtTm.LcnTm

s

-

30231

Rated active power WMaxOutRtg

RO

3

U32

FIX0

1

Device

Parameter.Inverter.WLim

W

50000 W

30233

Set active power limit

RO

2 / 3

U32

FIX0

1

Device

Parameter.Inverter.WMax

W

50000 W

30235

Backup mode status

RO

3

U32

TAGLIST

-

Device

Measurement.Operation.BckStt

1440: Grid mode
1441: Offgrid operation

1440: Grid mode

30237

Grid type

RO

3

U32

TAGLIST

-

AC Side

Measurement.GridMs.GriTyp

18007: 400 V/230 V, three line conductors and neutral conductor
18008: 480 V/277 V, three line conductors and neutral conductor
18011: 230 V/400 V, three line conductors and neutral conductor
18012: 380 V/220 V, three line conductors and neutral conductor
18023: 440 V/254 V, three line conductors and neutral conductor
18030: 420 V/242 V, three line conductors and neutral conductor
18033: 208 V/120 V, three line conductors and neutral conductor

18007: 400 V/230 V, three line conductors and neutral conductor

30239

PowerBalancer operating mode

RO

3

U32

TAGLIST

-

Device

Operation.PwrBal.OpMod

-

-

30247

Current event number for manufacturer

RO

3

U32

FIX0

1

Status

Operation.Evt.EvtNo

-

-

30249

Gfdi relay status

RO

3

U32

TAGLIST

-

Status

Operation.GfdiSwStt

-

-

30251

Block status

RO

3

U32

TAGLIST

-

Status

Measurement.Operation.RstrLokStt

16777213: Information not available

302: -------

30257

DC switch

RO

3

U32

TAGLIST

-

DC Side

Operation.DcSw.Stt

-

-

30267

DC switch

RO

3

U32

TAGLIST

-

DC Side

Operation.DcSw.Stt

-

-

30331

Error message DC switch

RO

3

U32

TAGLIST

-

DC Side

Operation.DcSw.Evt.Msg

-

-

30513

Total yield

RO

3

U64

FIX0

1

AC Side

Measurement.Metering.TotWhOut

Wh

-

30517

Daily yield

RO

3

U64

FIX0

1

AC Side

Metering.DyWhOut

Wh

-

30521

Operating time

RO

3

U64

DURATION

1

AC Side

Measurement.Metering.TotOpTms

s

-

30525

Feed-in time

RO

3

U64

DURATION

1

AC Side

Measurement.Metering.TotFeedTms

s

-

30529

Total yield

RO

3

U32

FIX0

1

AC Side

Measurement.Metering.TotWhOut

Wh

-

30531

Total yield

RO

3

U32

FIX0

1

AC Side

Measurement.Metering.TotWhOut

Wh

-

30533

Total yield

RO

3

U32

FIX0

1

AC Side

Measurement.Metering.TotWhOut

Wh

-

30535

Daily yield

RO

3

U32

FIX0

1

AC Side

Metering.DyWhOut

Wh

-

30537

Daily yield

RO

3

U32

FIX0

1

AC Side

Metering.DyWhOut

Wh

-

30539

Daily yield

RO

3

U32

FIX0

1

AC Side

Metering.DyWhOut

Wh

-

30541

Operating time

RO

3

U32

DURATION

1

AC Side

Measurement.Metering.TotOpTms

s

-

30543

Feed-in time

RO

3

U32

DURATION

1

AC Side

Measurement.Metering.TotFeedTms

s

-

30545

Fan operating time

RO

3

U32

DURATION

1

Device

Coolsys.FanCab1.AbsOpTms

s

-

30547

Fan 2 operating time

RO

3

U32

DURATION

1

Device

Coolsys.FanCab2.AbsOpTms

s

-

30549

Fan heat sink operating time

RO

3

U32

DURATION

1

Device

Coolsys.FanHs.AbsOpTms

s

-

30559

Number of events for user

RO

3

U32

FIX0

1

Status

Measurement.Operation.EvtCntUsr

-

-

30561

Number of events for installer

RO

3

U32

FIX0

1

Status

Measurement.Operation.EvtCntIstl

-

-

30563

Number of events for service

RO

3

U32

FIX0

1

Status

Operation.EvtCntSvc

-

-

30565

Number of generator starts

RO

3

U32

FIX0

1

Generator

Gn.Diag.StrCnt

-

-

30567

Amp hours counter for battery charge

RO

3

U32

FIX0

1

Battery

Bat.Diag.TotAhIn

Ah

-

30569

Amp hours counter for battery discharge

RO

3

U32

FIX0

1

Battery

Bat.Diag.TotAhOut

Ah

-

30571

Meter reading consumption meter

RO

3

U32

FIX0

1

AC Side

Metering.Csmp.TotWhIn

Wh

-

30573

Generator operating hours

RO

3

U32

DURATION

1

AC Side

Metering.GnMs.TotOpTms

s

-

30575

Generator output energy

RO

3

U32

FIX0

1

AC Side

Metering.GnMs.TotWhOutCalc

Wh

-

30577

Energy drawn today

RO

3

U32

FIX0

1

AC Side

Metering.GridMs.DyWhIn

Wh

-

30579

Energy fed into grid (today)

RO

3

U32

FIX0

1

AC Side

Metering.GridMs.DyWhOut

Wh

-

30581

Counter reading of power drawn counter

RO

3

U32

FIX0

1

AC Side

Metering.GridMs.TotWhIn

Wh

-

30583

Grid feed-in counter reading

RO

3

U32

FIX0

1

AC Side

Metering.GridMs.TotWhOut

Wh

-

30585

Power outage

RO

3

U32

DURATION

1

AC Side

Metering.GriFailTms

s

-

30587

PV generation counter reading

RO

3

U32

FIX0

1

AC Side

Metering.PvMs.TotWhOut

Wh

-

30589

Total increased self-consumption

RO

3

U32

FIX0

1

AC Side

Metering.SelfCsmp.AbsSelfCsmpInc

Wh

-

30591

Today's increased self-consumption

RO

3

U32

FIX0

1

AC Side

Metering.SelfCsmp.DySelfCsmpInc

Wh

-

30593

Energy consumed internally

RO

3

U32

FIX0

1

AC Side

Metering.SelfCsmp.SelfCsmpWh

Wh

-

30595

Absorbed energy

RO

3

U32

FIX0

1

AC Side

Metering.WhIn

Wh

-

30597

Released energy

RO

3

U32

FIX0

1

AC Side

Metering.WhOut

Wh

-

30599

Number of grid connections

RO

3

U32

FIX0

1

AC Side

Measurement.Operation.GriSwCnt

-

-

30601

Fan 3 operating time

RO

3

U32

DURATION

1

Device

Coolsys.FanCab3.AbsOpTms

s

-

30769

DC current input

RO

3

S32

FIX3

0.001

DC Side

DcMs.Amp

A

-

30771

DC voltage input

RO

3

S32

FIX2

0.01

DC Side

DcMs.Vol

V

-

30773

DC power input

RO

3

S32

FIX0

1

DC Side

DcMs.Watt

W

-

30775

Power

RO

2 / 3

S32

FIX0

1

AC Side

Measurement.GridMs.TotW

W

-

30777

Power L1

RO

3

S32

FIX0

1

AC Side

Measurement.GridMs.W.phsA

W

-

30779

Power L2

RO

3

S32

FIX0

1

AC Side

Measurement.GridMs.W.phsB

W

-

30781

Power L3

RO

3

S32

FIX0

1

AC Side

Measurement.GridMs.W.phsC

W

-

30783

Grid voltage phase L1

RO

3

U32

FIX2

0.01

AC Side

Measurement.GridMs.PhV.phsA

V

-

30785

Grid voltage phase L2

RO

3

U32

FIX2

0.01

AC Side

Measurement.GridMs.PhV.phsB

V

-

30787

Grid voltage phase L3

RO

3

U32

FIX2

0.01

AC Side

Measurement.GridMs.PhV.phsC

V

-

30789

Grid voltage phase L1 against L2

RO

3

U32

FIX2

0.01

AC Side

Measurement.GridMs.PhV.phsA2B

V

-

30791

Grid voltage phase L2 against L3

RO

3

U32

FIX2

0.01

AC Side

Measurement.GridMs.PhV.phsB2C

V

-

30793

Grid voltage phase L3 against L1

RO

3

U32

FIX2

0.01

AC Side

Measurement.GridMs.PhV.phsC2A

V

-

30795

Grid current

RO

3

U32

FIX3

0.001

AC Side

Measurement.GridMs.TotA

A

-

30797

Grid current phase L1

RO

3

U32

FIX3

0.001

AC Side

Measurement.GridMs.A.phsA

A

-

30799

Grid current phase L2

RO

3

U32

FIX3

0.001

AC Side

Measurement.GridMs.A.phsB

A

-

30801

Grid current phase L3

RO

3

U32

FIX3

0.001

AC Side

Measurement.GridMs.A.phsC

A

-

30803

Grid frequency

RO

3

U32

FIX2

0.01

AC Side

Measurement.GridMs.Hz

Hz

-

30805

Reactive power

RO

2 / 3

S32

FIX0

1

AC Side

Measurement.GridMs.TotVAr

var

-

30807

Reactive power L1

RO

3

S32

FIX0

1

AC Side

Measurement.GridMs.VAr.phsA

var

-

30809

Reactive power L2

RO

3

S32

FIX0

1

AC Side

Measurement.GridMs.VAr.phsB

var

-

30811

Reactive power L3

RO

3

S32

FIX0

1

AC Side

Measurement.GridMs.VAr.phsC

var

-

30813

Apparent power

RO

3

S32

FIX0

1

AC Side

Measurement.GridMs.TotVA

VA

-

30815

Apparent power L1

RO

3

S32

FIX0

1

AC Side

Measurement.GridMs.VA.phsA

VA

-

30817

Apparent power L2

RO

3

S32

FIX0

1

AC Side

Measurement.GridMs.VA.phsB

VA

-

30819

Apparent power L3

RO

3

S32

FIX0

1

AC Side

Measurement.GridMs.VA.phsC

VA

-

30821

Displacement power factor

RO

3

U32

FIX2

0.01

AC Side

GridMs.TotPF

-

-

30823

Excitation type of cos φ

RO

3

U32

TAGLIST

-

AC Side

Measurement.GridMs.TotPFExt

1041: Overexcited
1042: Underexcited

1042: Underexcited

30825

Operating mode of static voltage stability, configuration of static voltage stability

RO

3

U32

TAGLIST

-

System and device control

Inverter.VArModCfg.VArMod

-

-

30827

Manual reactive power setting for active power output

RO

2 / 3

S32

FIX0

1

System and device control

Parameter.Inverter.VArModCfg.VArCnstCfg.VAr

var

-

30829

Manual reactive power setting for active power output

RO

2 / 3

S32

FIX1

0.1

System and device control

Parameter.Inverter.VArModCfg.VArCnstCfg.VArNom

%

-

30831

cos φ setpoint, cos φ config., direct specif.

RO

3

S32

FIX2

0.01

System and device control

Inverter.VArModCfg.PFCnstCfg.PF

-

-

30833

cos φ excit.type, cos φ config., direct spec.

RO

3

U32

TAGLIST

-

System and device control

Inverter.VArModCfg.PFCnstCfg.PFExt

-

-

30835

Operating mode active power setting

RO

3

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WMod

303: Off
1077: Manual setting in W
1078: Manual setting in %
1079: External active power setpoint
4490: External active power setting 2
40471: External active power setting 1

1079: External active power setpoint

30837

Active power limitation P, active power configuration

RO

3

U32

FIX0

1

System and device control

Parameter.Inverter.WModCfg.WCnstCfg.W

W

-

30839

Active power limitation P, active power configuration

RO

3

U32

FIX0

1

System and device control

Parameter.Inverter.WModCfg.WCnstCfg.WNom

%

-

30843

Battery current

RO

3

S32

FIX3

0.001

Battery

Measurement.Bat.Amp

A

-

30845

Current battery state of charge

RO

2 / 3

U32

FIX0

1

Battery

Measurement.Bat.ChaStt

%

-

30847

Current battery capacity

RO

3

U32

FIX0

1

Battery

Measurement.Bat.Diag.ActlCapacNom

%

-

30849

Battery temperature

RO

3

S32

TEMPERATURE

0.1

Battery

Measurement.Bat.TmpVal

°C

-

30851

Battery voltage

RO

3

U32

FIX2

0.01

Battery

Measurement.Bat.Vol

V

-

30853

Active battery charging mode

RO

3

U32

TAGLIST

-

Battery

Cha.ActChaMod

-

-

30855

Current battery charging set voltage

RO

3

U32

FIX2

0.01

Battery

Cha.ActlChaVolSpt

V

-

30857

Number of battery charge throughputs

RO

3

S32

FIX0

1

Battery

Bat.Diag.CapacThrpCnt

-

-

30859

Battery maint. state of charge

RO

3

U32

TAGLIST

-

Battery

Maint.FulEqCha

-

-

30861

Load power

RO

3

S32

FIX0

1

AC Side

Metering.Csmp.TotWIn

W

-

30863

Current generator performance

RO

3

U32

FIX0

1

Generator

GnMs.TotWOut

W

-

30865

Power drawn

RO

3

S32

FIX0

1

AC Side

Metering.GridMs.TotWIn

W

-

30867

Power grid feed-in

RO

3

S32

FIX0

1

AC Side

Metering.GridMs.TotWOut

W

-

30869

PV power generated

RO

3

S32

FIX0

1

AC Side

Metering.PvMs.TotWOut

W

-

30871

Current self-consumption

RO

3

U32

FIX0

1

AC Side

Metering.SelfCsmp.ActlSelfCsmp

W

-

30873

Current rise in self-consumption

RO

3

S32

FIX0

1

AC Side

Metering.SelfCsmp.SelfCsmpInc

W

-

30875

Multifunction relay status

RO

3

U32

TAGLIST

-

Device

MltFncSw.Stt

-

-

30877

Power supply status

RO

3

U32

TAGLIST

-

AC Side

Operation.CsmpGriConnStt

-

-

30879

Reason for generator request

RO

3

U32

TAGLIST

-

Generator

Operation.GnDmdReas

-

-

30881

Plant mains connection

RO

3

U32

TAGLIST

-

AC Side

Measurement.Operation.PvGriConn

1779: Separated
1780: Public electricity mains
1781: Island mains

1779: Separated

30883

Status of utility grid

RO

3

U32

TAGLIST

-

AC Side

PubGri.Stt

-

-

30885

Output external grid connection

RO

3

U32

FIX0

1

AC Side

ExtGridMs.TotW

W

-

30887

Output external grid connection phase A

RO

3

U32

FIX0

1

AC Side

ExtGridMs.W.phsA

W

-

30889

Output external grid connection phase B

RO

3

U32

FIX0

1

AC Side

ExtGridMs.W.phsB

W

-

30891

Output external grid connection phase C

RO

3

U32

FIX0

1

AC Side

ExtGridMs.W.phsC

W

-

30893

Reactive power external grid connection

RO

3

U32

FIX0

1

AC Side

ExtGridMs.TotVAr

var

-

30895

Reactive power external grid connection phase A

RO

3

U32

FIX0

1

AC Side

ExtGridMs.VAr.phsA

var

-

30897

Reactive power external grid connection phase B

RO

3

U32

FIX0

1

AC Side

ExtGridMs.VAr.phsB

var

-

30899

Reactive power external grid connection phase C

RO

3

U32

FIX0

1

AC Side

ExtGridMs.VAr.phsC

var

-

30901

Grid frequency of external grid connection

RO

3

U32

FIX2

0.01

AC Side

ExtGridMs.Hz

Hz

-

30903

Voltage external grid connection phase A

RO

3

U32

FIX2

0.01

AC Side

ExtGridMs.PhV.phsA

V

-

30905

Voltage external grid connection phase B

RO

3

U32

FIX2

0.01

AC Side

ExtGridMs.PhV.phsB

V

-

30907

Voltage external grid connection phase C

RO

3

U32

FIX2

0.01

AC Side

ExtGridMs.PhV.phsC

V

-

30909

Electricity external grid connection phase A

RO

3

S32

FIX3

0.001

AC Side

ExtGridMs.A.phsA

A

-

30911

Electricity external grid connection phase B

RO

3

S32

FIX3

0.001

AC Side

ExtGridMs.A.phsB

A

-

30913

Electricity external grid connection phase C

RO

3

S32

FIX3

0.001

AC Side

ExtGridMs.A.phsC

A

-

30915

Power supply status

RO

3

U32

TAGLIST

-

AC Side

Operation.CsmpGriConnStt

-

-

30917

Generator status

RO

3

U32

TAGLIST

-

Generator

Gn.OpStt

-

-

30919

Oper.mode vol.maint.at Q on Dem., st.vol.maint.conf.

RO

3

U32

TAGLIST

-

System and device control

Inverter.VArModCfg.VArModDmd

-

-

30921

Manual reactive power setpoint for zero power output

RO

2 / 3

S32

FIX0

1

System and device control

Parameter.Inverter.VArModCfg.VArCnstCfgDmd.VAr

var

-

30923

Manual reactive power setpoint for zero power output

RO

2 / 3

S32

FIX1

0.1

System and device control

Parameter.Inverter.VArModCfg.VArCnstCfgDmd.VArNom

%

-

30925

Connection speed of SMACOM A

RO

3

U32

TAGLIST

-

System communication

Spdwr.ComSocA.ConnSpd

-

-

30927

Duplex mode of SMACOM A

RO

3

U32

TAGLIST

-

System communication

Spdwr.ComSocA.DpxMode

-

-

30929

Speedwire connection status of SMACOM A

RO

3

U32

TAGLIST

-

System communication

Measurement.Spdwr.ComSocA.Stt

35: Fault
307: Ok
455: Warning
1725: No connection

307: Ok

30931

Connection speed of SMACOM B

RO

3

U32

TAGLIST

-

System communication

Spdwr.ComSocB.ConnSpd

-

-

30933

Duplex mode of SMACOM B

RO

3

U32

TAGLIST

-

System communication

Spdwr.ComSocB.DpxMode

-

-

30935

Speedwire connection status of SMACOM B

RO

3

U32

TAGLIST

-

System communication

Spdwr.ComSocB.Stt

-

-

30937

Connection speed of SMACOM C

RO

3

U32

TAGLIST

-

System communication

Spdwr.ComSocC.ConnSpd

-

-

30939

Duplex mode of SMACOM C

RO

3

U32

TAGLIST

-

System communication

Spdwr.ComSocC.DpxMode

-

-

30941

Speedwire connection status of SMACOM C

RO

3

U32

TAGLIST

-

System communication

Spdwr.ComSocC.Stt

-

-

30943

Connection speed of SMACOM D

RO

3

U32

TAGLIST

-

System communication

Spdwr.ComSocD.ConnSpd

-

-

30945

Duplex mode of SMACOM D

RO

3

U32

TAGLIST

-

System communication

Spdwr.ComSocD.DpxMode

-

-

30947

Speedwire connection status of SMACOM D

RO

3

U32

TAGLIST

-

System communication

Spdwr.ComSocD.Stt

-

-

30949

Displacement power factor

RO

3

U32

FIX3

0.001

AC Side

Measurement.GridMs.TotPFPrc

-

-

30951

DC power input

RO

3

S32

FIX0

1

DC Side

DcMs.Watt

W

-

30953

Internal temperature

RO

3

S32

TEMPERATURE

0.1

Device

Coolsys.Cab.TmpVal

°C

-

30955

Battery oper. status

RO

3

U32

TAGLIST

-

Battery

Measurement.Bat.OpStt

303: Off
2291: Battery standby
2292: Charge battery
2293: Discharge battery

2291: Battery standby

30975

Intermediate circuit voltage

RO

3

S32

FIX2

0.01

Device

Inverter.DclVol

V

-

30977

Grid current phase L1

RO

3

S32

FIX3

0.001

AC Side

Measurement.GridMs.A.phsA

A

-

30979

Grid current phase L2

RO

3

S32

FIX3

0.001

AC Side

Measurement.GridMs.A.phsB

A

-

30981

Grid current phase L3

RO

3

S32

FIX3

0.001

AC Side

Measurement.GridMs.A.phsC

A

-

30983

Output of photovoltaics

RO

3

U32

FIX0

1

DC Side

Metering.PvChaMs.TotWPv

W

-

30985

Total current external network connection

RO

3

S32

FIX3

0.001

AC Side

ExtGridMs.TotA

A

-

30987

Fault battery state of charge

RO

3

U32

FIX1

0.1

Battery

Bat.BatChaDif

%

-

30989

Maximum battery current in charge direction

RO

3

U32

FIX3

0.001

Battery

Bat.Diag.ChaAMax

A

-

30991

Maximum battery current in discharge direction

RO

3

U32

FIX3

0.001

Battery

Bat.Diag.DschAMax

A

-

30993

Charge factor: ratio of battery charge/discharge

RO

3

U32

FIX3

0.001

Battery

Bat.Diag.ChaFact

-

-

30995

Operating time of battery statistics counter

RO

3

U32

DURATION

1

Battery

Bat.Diag.StatTm

s

-

30997

Lowest measured battery temperature

RO

3

S32

TEMPERATURE

0.1

Battery

Bat.Diag.TmpValMin

°C

-

30999

Highest measured battery temperature

RO

3

S32

TEMPERATURE

0.1

Battery

Bat.Diag.TmpValMax

°C

-

31001

Max. occurred battery voltage

RO

3

U32

FIX2

0.01

Battery

Bat.Diag.VolMax

V

-

31003

Remaining time until full charge

RO

3

U32

DURATION

1

Battery

Bat.FulChaRmgTm

s

-

31005

Remaining time until equalization charge

RO

3

U32

DURATION

1

Battery

Bat.EqChaRmgTm

s

-

31007

Remaining absorption time

RO

3

U32

DURATION

1

Battery

Bat.RmgChaTm

s

-

31009

Lower discharge limit for self-consumption range

RO

3

U32

FIX0

1

Battery

BatUsDm.SelfCsmpDmLim

%

-

31011

Total output current of solar charger

RO

3

U32

FIX3

0.001

DC Side

Metering.PvChaMs.Amp

A

-

31013

Remaining min. operating time of generator

RO

3

U32

DURATION

1

Generator

Operation.RmgMinRunTm

s

-

31015

Operating status Master (Phase L1)

RO

3

U32

TAGLIST

-

Status

Operation.Health.Master

-

-

31017

Current speedwire IP address

RO

3

TEXT

UTF_8

-

System communication

Parameter.Spdwr.ActlIp

-

-

31025

Current speedwire subnet mask

RO

3

TEXT

UTF_8

-

System communication

Parameter.Spdwr.ActlSnetMsk

-

-

31033

Current speedwire gateway address

RO

3

TEXT

UTF_8

-

System communication

Parameter.Spdwr.ActlGwIp

-

-

31041

Current speedwire DNS server address

RO

3

TEXT

UTF_8

-

System communication

Parameter.Spdwr.ActlDnsSrvIp

-

-

31049

Slave 1: Multifunction relay status

RO

3

U32

TAGLIST

-

Device

MltFncSw.SttSlv1

-

-

31051

Slave 2: Multifunction relay status

RO

3

U32

TAGLIST

-

Device

MltFncSw.SttSlv2

-

-

31053

Operating status Slave1 (Phase L2)

RO

3

U32

TAGLIST

-

Status

Operation.Health.Slv1

-

-

31055

Operating status Slave2 (Phase L3)

RO

3

U32

TAGLIST

-

Status

Operation.Health.Slv2

-

-

31057

Status battery application area

RO

3

U32

TAGLIST

-

Battery

BatUsDm.Stt

-

-

31059

Absorption phase active

RO

3

U32

TAGLIST

-

Battery

Bat.AbsPhsAct

-

-

31061

Control of battery charging via communication available

RO

3

U32

TAGLIST

-

Battery

Bat.ChaCtlComAval

-

-

31063

Total energy of photovoltaics

RO

3

U32

FIX0

1

DC Side

Metering.PvChaMs.TotWhPv

Wh

-

31065

Total energy of photovoltaics current day

RO

3

U32

FIX0

1

DC Side

Metering.PvChaMs.DyWhPv

Wh

-

31067

Number of battery equalization charges

RO

3

U32

FIX0

1

Battery

Cha.EqChaCnt

-

-

31069

Number of battery full charges

RO

3

U32

FIX0

1

Battery

Cha.FulChaCnt

-

-

31071

Relative battery discharge since last full charge

RO

3

U32

FIX0

1

Battery

Cha.FulDschNom

%

-

31073

Relative battery discharge since last equalization charge

RO

3

U32

FIX0

1

Battery

Cha.EqDschNom

%

-

31075

Operating time energy count

RO

3

U32

DURATION

1

AC Side

Metering.EnCntTm

s

-

31077

Photovoltaic energy in solar charger

RO

3

U32

FIX0

1

DC Side

Metering.PvChaMs.TotWhSICha

Wh

-

31085

Nominal power in Ok Mode

RO

3

U32

FIX0

1

Status

Measurement.Operation.HealthStt.Ok

W

-

31089

Reset measured values

RO

3

U32

TAGLIST

-

Device

Operation.ValRsUsr

-

-

31091

PV energy produced (today)

RO

3

U32

FIX0

1

AC Side

Metering.PvMs.DyWhFeed

Wh

-

31093

PV energy produced (yesterday)

RO

3

U32

FIX0

1

AC Side

Metering.PvMs.PreDyWhFeed

Wh

-

31095

PV energy produced (current month)

RO

3

U32

FIX0

1

AC Side

Metering.PvMs.MthWhFeed

Wh

-

31097

PV energy produced (last month)

RO

3

U32

FIX0

1

AC Side

Metering.PvMs.PreMthWhFeed

Wh

-

31099

Generator energy produced (today)

RO

3

U32

FIX0

1

AC Side

Metering.GnMs.DyWhFeed

Wh

-

31101

Generator energy produced (yesterday)

RO

3

U32

FIX0

1

AC Side

Metering.GnMs.PreDyWhFeed

Wh

-

31103

Generator energy produced (current month)

RO

3

U32

FIX0

1

AC Side

Metering.GnMs.MthWhFeed

Wh

-

31105

Generator energy produced (last month)

RO

3

U32

FIX0

1

AC Side

Metering.GnMs.PreMthWhFeed

Wh

-

31107

Grid feed-in today

RO

3

U32

FIX0

1

AC Side

Metering.GridMs.DyWhFeed

Wh

-

31109

Energy output to grid (yesterday)

RO

3

U32

FIX0

1

AC Side

Metering.GridMs.PreDyWhFeed

Wh

-

31111

Energy output to grid (current month)

RO

3

U32

FIX0

1

AC Side

Metering.GridMs.MthWhFeed

Wh

-

31113

Energy output to grid (last month)

RO

3

U32

FIX0

1

AC Side

Metering.GridMs.PreMthWhFeed

Wh

-

31115

Energy drawn from grid (yesterday)

RO

3

U32

FIX0

1

AC Side

Metering.GridMs.PreDyWhIn

Wh

-

31117

Energy drawn from grid (current month)

RO

3

U32

FIX0

1

AC Side

Metering.GridMs.MthWhIn

Wh

-

31119

Energy drawn from grid (last month)

RO

3

U32

FIX0

1

AC Side

Metering.GridMs.PreMthWhIn

Wh

-

31121

Energy consumed (today)

RO

3

U32

FIX0

1

AC Side

Metering.Csmp.DyWhIn

Wh

-

31123

Energy consumed (yesterday)

RO

3

U32

FIX0

1

AC Side

Metering.Csmp.PreDyWhIn

Wh

-

31125

Energy consumed (current month)

RO

3

U32

FIX0

1

AC Side

Metering.Csmp.MthWhIn

Wh

-

31127

Energy consumed (last month)

RO

3

U32

FIX0

1

AC Side

Metering.Csmp.PreMthWhIn

Wh

-

31129

PV power not requested

RO

3

S32

FIX0

1

AC Side

Operation.NotUsW

W

-

31131

Available PV power

RO

3

S32

FIX0

1

AC Side

Operation.CurMaxW

W

-

31133

Internal PV power limitation

RO

3

S32

FIX0

1

System and device control

Inverter.CurWCtl

W

-

31135

Reactive power of loads

RO

3

S32

FIX0

1

AC Side

Metering.Csmp.TotVArIn

var

-

31137

Maximum short-term decrease in power

RO

3

S32

FIX0

1

AC Side

Operation.WDecMaxShrt

W

-

31139

PV reactive power currently supplied from grid

RO

3

S32

FIX0

1

AC Side

Metering.PvMs.TotVArOut

var

-

31141

PV apparent power currently supplied from grid

RO

3

S32

FIX0

1

AC Side

Metering.PvMs.TotVAOut

VA

-

31143

Return monitoring value

RO

3

S32

FIX0

1

System communication

Sys.ComWdOut

-

-

31145

Number of battery strings present

RO

3

U32

FIX0

1

Battery

Bat.StrgCnt

-

-

31147

Number of active battery strings

RO

3

U32

FIX0

1

Battery

Bat.StrgCntAct

-

-

31149

Waiting time until feed-in

RO

3

U32

DURATION

1

Status

Inverter.RmgTms

s

-

31151

Average voltage on the high-voltage side

RO

3

U32

FIX2

0.01

AC Side

Trf.HiVol

V

-

31153

Average current on the high-voltage side

RO

3

S32

FIX3

0.001

AC Side

Trf.HiA

A

-

31155

Current assigned active power

RO

3

U32

FIX0

1

System and device control

Operation.Dmd.WSpt

W

-

31157

Current assigned apparent power

RO

3

U32

FIX0

1

System and device control

Operation.Dmd.VASpt

W

-

31159

Current spec. reactive power Q

RO

3

S32

FIX0

1

System and device control

Operation.Dmd.VArCtl

var

-

31161

Power of inverter

RO

3

S32

FIX0

1

AC Side

Inverter.TotW

W

-

31163

Apparent power of inverter

RO

3

S32

FIX0

1

AC Side

Inverter.TotVAr

var

-

31165

Insulation resistance of battery

RO

3

U32

FIX0

1

DC Side

Bat.LeakRis

Ohm

-

31167

Insulation resistance of inverter

RO

3

U32

FIX0

1

DC Side

Inverter.LeakRis

Ohm

-

31169

Charge energy (today)

RO

3

U32

FIX0

1

AC Side

Metering.BatMs.DyWhCha

Wh

-

31171

Charge energy (yesterday)

RO

3

U32

FIX0

1

AC Side

Metering.BatMs.PreDyWhCha

Wh

-

31173

Charge energy (current month)

RO

3

U32

FIX0

1

AC Side

Metering.BatMs.MthWhCha

Wh

-

31175

Charge energy (previous month)

RO

3

U32

FIX0

1

AC Side

Metering.BatMs.PreMthWhCha

Wh

-

31177

Discharge energy (today)

RO

3

U32

FIX0

1

AC Side

Metering.BatMs.DyWhDsch

Wh

-

31179

Discharge energy (yesterday)

RO

3

U32

FIX0

1

AC Side

Metering.BatMs.PreDyWhDsch

Wh

-

31181

Discharge energy (current month)

RO

3

U32

FIX0

1

AC Side

Metering.BatMs.MthWhDsch

Wh

-

31183

Discharge energy (previous month)

RO

3

U32

FIX0

1

AC Side

Metering.BatMs.PreMthWhDsch

Wh

-

31185

Charge energy (total)

RO

3

U32

FIX0

1

AC Side

Metering.BatMs.TotWhIn

Wh

-

31187

Discharge energy (total)

RO

3

U32

FIX0

1

AC Side

Metering.BatMs.TotWhOut

Wh

-

31189

Mean value of the external conductor voltages

RO

3

U32

FIX2

0.01

AC Side

GridMs.AvVol

V

-

31191

Supplied battery power in all phases

RO

3

S32

FIX0

1

AC Side

Metering.BatMs.TotWOut

W

-

31193

Consumed battery power in all phases

RO

3

S32

FIX0

1

AC Side

Metering.BatMs.TotWIn

W

-

31195

Supplied reactive battery power in all phases

RO

3

S32

FIX0

1

AC Side

Metering.BatMs.TotVArOut

var

-

31197

Calculated active power default value for battery inverter

RO

3

S32

FIX0

1

System and device control

Operation.BatDmd.CalcWCtl

W

-

31199

Calculated reactive power default value for battery inverter

RO

3

S32

FIX0

1

System and device control

Operation.BatDmd.CalcVArCtl

var

-

31201

Power of all battery inverters in OK status

RO

3

S32

FIX0

1

Status

Operation.BatHealthStt.Ok

W

-

31203

Free capacity of all batteries

RO

3

U32

FIX0

1

Battery

Bat.TotAvalCha

Wh

-

31205

Accessible charge of all batteries

RO

3

U32

FIX0

1

Battery

Bat.TotAvalDsch

Wh

-

31207

Counter state of generator generating meter

RO

3

U32

FIX0

1

AC Side

Metering.GnMs.TotWhOut

Wh

-

31221

EEI displacement power factor

RO

3

S32

FIX3

0.001

AC Side

Measurement.GridMs.TotPFEEI

-

-

31223

Current generator reactive power

RO

3

S32

FIX0

1

AC Side

Metering.GnMs.TotVArOut

var

-

31225

Current generator reactive power

RO

3

S32

FIX0

1

Generator

GnMs.TotVArOut

W

-

31227

Supplied battery power in all phases

RO

3

S32

FIX0

1

AC Side

BatMs.TotWOut

W

-

31229

Consumed battery power in all phases

RO

3

S32

FIX0

1

AC Side

BatMs.TotWIn

W

-

31231

Supplied reactive battery power in all phases

RO

3

S32

FIX0

1

AC Side

BatMs.TotVArOut

var

-

31233

Reactive power supplied to the grid in all phases

RO

3

S32

FIX0

1

AC Side

Metering.GridMs.TotVArOut

var

-

31235

Setpoint of active power limitation via dialog input

RO

3

U32

FIX2

0.01

System and device control

InOut.DigIn.CurWCtlNom

%

-

31237

Setpoint for active power limitation via analog input

RO

3

U32

FIX2

0.01

System and device control

InOut.AnIn.CurWCtlNom

%

-

31239

PV power limitation via communication

RO

3

U32

FIX2

0.01

System and device control

Inverter.CurWCtlComNom

%

-

31241

PV power limitation via communication for direct marketing

RO

2

U32

FIX2

0.01

System and device control

Measurement.Inverter.CurWCtlDrkNom

%

-

31243

Minimum PV power limitation

RO

3

U32

FIX2

0.01

System and device control

Inverter.CurWCtlMinNom

%

-

31245

Internal PV power limitation

RO

2

U32

FIX2

0.01

System and device control

Measurement.Inverter.CurWCtlNom

%

-

31247

Residual current

RO

3

S32

FIX3

0.001

DC Side

Measurement.Isolation.FltA

A

-

31249

System active power at grid connection point

RO

2

S32

FIX0

1

Grid connection

Measurement.Metering.PCCMs.PlntW

W

-

31251

System reactive power at grid connection point

RO

2

S32

FIX0

1

Grid connection

Measurement.Metering.PCCMs.PlntVAr

var

-

31253

Grid voltage phase L1

RO

3

U32

FIX2

0.01

AC Side

Metering.GridMs.PhV.phsA

V

-

31255

Grid voltage phase L2

RO

3

U32

FIX2

0.01

AC Side

Metering.GridMs.PhV.phsB

V

-

31257

Grid voltage phase L3

RO

3

U32

FIX2

0.01

AC Side

Metering.GridMs.PhV.phsC

V

-

31259

Power grid feeding L1

RO

3

U32

FIX0

1

AC Side

Metering.GridMs.W.phsA

W

-

31261

Power grid feeding L2

RO

3

U32

FIX0

1

AC Side

Metering.GridMs.W.phsB

W

-

31263

Power grid feeding L3

RO

3

U32

FIX0

1

AC Side

Metering.GridMs.W.phsC

W

-

31265

Power drawn from grid phase L1

RO

3

U32

FIX0

1

AC Side

Metering.GridMs.WIn.phsA

W

-

31267

Power drawn from grid phase L2

RO

3

U32

FIX0

1

AC Side

Metering.GridMs.WIn.phsB

W

-

31269

Power drawn from grid phase L3

RO

3

U32

FIX0

1

AC Side

Metering.GridMs.WIn.phsC

W

-

31271

Reactive power grid feeding phase L1

RO

3

S32

FIX0

1

AC Side

Metering.GridMs.VAr.phsA

var

-

31273

Reactive power grid feeding phase L2

RO

3

S32

FIX0

1

AC Side

Metering.GridMs.VAr.phsB

var

-

31275

Reactive power grid feeding phase L3

RO

3

S32

FIX0

1

AC Side

Metering.GridMs.VAr.phsC

var

-

31277

Reactive power grid feeding

RO

3

S32

FIX0

1

AC Side

Metering.GridMs.TotVAr

var

-

31377

Battery manufacturer

RO

3

U32

TAGLIST

-

Type Label

Nameplate.Bat.Vendor

-

-

31379

BMS type

RO

3

U32

TAGLIST

-

Device Components

Nameplate.CmpBMS.Typ

-

-

31381

BMS serial number

RO

3

TEXT

UTF_8

-

Device Components

Parameter.Nameplate.CmpBMS.SerNumTxt

-

-

31389

BMS firmware version

RO

3

U32

FW_VERSION

1

Device Components

Parameter.Nameplate.CmpBMS.SwRev

-

-

31391

Battery status

RO

3

U32

TAGLIST

-

Status

Measurement.Operation.Bat.Health

35: Fault
303: Off
307: Ok
455: Warning

307: Ok

31393

Present battery charge

RO

3

U32

FIX0

1

Battery

Measurement.BatChrg.CurBatCha

W

-

31395

Present battery discharge

RO

3

U32

FIX0

1

Battery

Measurement.BatDsch.CurBatDsch

W

-

31397

Battery charge

RO

3

U64

FIX0

1

Battery

Measurement.BatChrg.BatChrg

Wh

-

31401

Battery discharge

RO

3

U64

FIX0

1

Battery

Measurement.BatDsch.BatDsch

Wh

-

31405

Current spec. active power limitation P

RO

2

U32

FIX0

1

System and device control

Measurement.Operation.Dmd.WCtl

W

-

31407

Current spec. cos φ

RO

3

U32

FIX4

0.0001

System and device control

Operation.Dmd.PFCtl

-

-

31409

Current spec. stimulation type cos φ

RO

3

U32

TAGLIST

-

System and device control

Operation.Dmd.PFExtCtl

-

-

31411

Current spec. reactive power Q

RO

3

S32

FIX0

1

System and device control

Operation.Dmd.VArCtl

var

-

31417

Output external grid connection

RO

3

S32

FIX0

1

AC Side

ExtGridMs.TotW

W

-

31419

Output external grid connection phase A

RO

3

S32

FIX0

1

AC Side

ExtGridMs.W.phsA

W

-

31421

Output external grid connection phase B

RO

3

S32

FIX0

1

AC Side

ExtGridMs.W.phsB

W

-

31423

Output external grid connection phase C

RO

3

S32

FIX0

1

AC Side

ExtGridMs.W.phsC

W

-

31425

Reactive power external grid connection

RO

3

S32

FIX0

1

AC Side

ExtGridMs.TotVAr

var

-

31427

Reactive power external grid connection phase A

RO

3

S32

FIX0

1

AC Side

ExtGridMs.VAr.phsA

var

-

31429

Reactive power external grid connection phase B

RO

3

S32

FIX0

1

AC Side

ExtGridMs.VAr.phsB

var

-

31431

Reactive power external grid connection phase C

RO

3

S32

FIX0

1

AC Side

ExtGridMs.VAr.phsC

var

-

31433

Displacement power factor

RO

3

U32

FIX2

0.01

AC Side

Metering.GridMs.TotPF

-

-

31435

Grid current phase L1

RO

3

S32

FIX3

0.001

AC Side

Metering.GridMs.A.phsA

A

-

31437

Grid current phase L2

RO

3

S32

FIX3

0.001

AC Side

Metering.GridMs.A.phsB

A

-

31439

Grid current phase L3

RO

3

S32

FIX3

0.001

AC Side

Metering.GridMs.A.phsC

A

-

31441

Apparent power L1

RO

3

S32

FIX0

1

AC Side

Metering.GridMs.VA.phsA

VA

-

31443

Apparent power L2

RO

3

S32

FIX0

1

AC Side

Metering.GridMs.VA.phsB

VA

-

31445

Apparent power L3

RO

3

S32

FIX0

1

AC Side

Metering.GridMs.VA.phsC

VA

-

31447

Grid frequency

RO

3

U32

FIX2

0.01

AC Side

Metering.GridMs.Hz

Hz

-

31449

Grid voltage phase L3 against L1

RO

3

U32

FIX2

0.01

AC Side

Metering.GridMs.PhV.phsC2A

V

-

31451

Grid voltage phase L1 against L2

RO

3

U32

FIX2

0.01

AC Side

Metering.GridMs.PhV.phsA2B

V

-

31453

Grid voltage phase L2 against L3

RO

3

U32

FIX2

0.01

AC Side

Metering.GridMs.PhV.phsB2C

V

-

31455

Apparent power

RO

3

S32

FIX0

1

AC Side

Metering.GridMs.TotVA

VA

-

31497

Reactive power

RO

2 / 3

S32

FIX0

1

AC Side

Measurement.GridMs.TotVAr

var

-

31499

EEI displacement power factor

RO

3

S32

FIX3

0.001

AC Side

Metering.GridMs.TotPFEEI

-

-

31501

Excitation type of cos φ

RO

3

U32

TAGLIST

-

AC Side

Metering.GridMs.TotPFExt

-

-

31503

Power Grid feed-in Line conductor L1 at point of interconnection

RO

2

S32

FIX0

1

Grid connection

Measurement.Metering.PCCMs.PlntW.phsA

W

-

31505

Power Grid feed-in Line conductor L2 at point of interconnection

RO

2

S32

FIX0

1

Grid connection

Measurement.Metering.PCCMs.PlntW.phsB

W

-

31507

Power Grid feed-in Line conductor L3 at point of interconnection

RO

2

S32

FIX0

1

Grid connection

Measurement.Metering.PCCMs.PlntW.phsC

W

-

31509

Reactive power Grid feed-in Line conductor L1 at point of interconnection

RO

2

S32

FIX0

1

Grid connection

Measurement.Metering.PCCMs.PlntVAr.phsA

var

-

31511

Reactive power Grid feed-in Line conductor L2 at point of interconnection

RO

2

S32

FIX0

1

Grid connection

Measurement.Metering.PCCMs.PlntVAr.phsB

var

-

31513

Reactive power Grid feed-in Line conductor L3 at point of interconnection

RO

2

S32

FIX0

1

Grid connection

Measurement.Metering.PCCMs.PlntVAr.phsC

var

-

31515

Grid voltage Line conductor L1 against L2 at point of interconnection

RO

3

U32

FIX2

0.01

Grid connection

Metering.PCCMs.PlntPhV.phsA2B

V

-

31517

Grid voltage Line conductor L2 against L3 at point of interconnection

RO

3

U32

FIX2

0.01

Grid connection

Metering.PCCMs.PlntPhV.phsB2C

V

-

31519

Grid voltage Line conductor L3 against L1 at point of interconnection

RO

3

U32

FIX2

0.01

Grid connection

Metering.PCCMs.PlntPhV.phsC2A

V

-

31521

Mean value Grid voltage L-N at point of interconnection

RO

3

U32

FIX2

0.01

Grid connection

Metering.PCCMs.PlntPhV.AvgLN

V

-

31523

Mean value Grid voltage L-L at point of interconnection

RO

3

U32

FIX2

0.01

Grid connection

Metering.PCCMs.PlntPhV.AvgLL

V

-

31525

Displacement power factor at point of interconnection

RO

2

S32

FIX2

0.01

Grid connection

Measurement.Metering.PCCMs.PlntPF

-

-

31527

Grid frequency at point of interconnection

RO

3

U32

FIX2

0.01

Grid connection

Metering.PCCMs.PlntHz

Hz

-

31529

PV system voltage phase L1

RO

2

U32

FIX2

0.01

Grid connection

Measurement.Metering.PCCMs.PlntPhV.phsA

V

-

31531

PV system voltage phase L2

RO

2

U32

FIX2

0.01

Grid connection

Measurement.Metering.PCCMs.PlntPhV.phsB

V

-

31533

PV system voltage phase L3

RO

2

U32

FIX2

0.01

Grid connection

Measurement.Metering.PCCMs.PlntPhV.phsC

V

-

31535

Output current Grid feed-in Line conductor L1 at point of interconnection

RO

2

S32

FIX3

0.001

Grid connection

Measurement.Metering.PCCMs.PlntA.phsA

A

-

31537

Output current Grid feed-in Line conductor L2 at point of interconnection

RO

2

S32

FIX3

0.001

Grid connection

Measurement.Metering.PCCMs.PlntA.phsB

A

-

31539

Output current Grid feed-in Line conductor L3 at point of interconnection

RO

2

S32

FIX3

0.001

Grid connection

Measurement.Metering.PCCMs.PlntA.phsC

A

-

31541

Mean value Grid voltage Line conductor L-N

RO

3

U32

FIX2

0.01

AC Side

Metering.GridMs.PhV.AvgLN

V

-

31543

Mean value Grid voltage Line conductor L-L

RO

3

U32

FIX2

0.01

AC Side

Metering.GridMs.PhV.AvgLL

V

-

31545

Available system power

RO

3

U32

FIX0

1

System and device control

Operation.WAval

W

-

31547

Available inverter power

RO

2

U32

FIX0

1

Device

Measurement.Inverter.WAval

W

-

31585

Present battery charge

RO

3

U32

FIX0

1

Battery

BatChrg.CurBatChaArr

W

-

31591

Present battery discharge

RO

3

U32

FIX0

1

Battery

BatDsch.CurBatDschArr

W

-

31597

Battery charge

RO

3

U64

FIX0

1

Battery

BatChrg.BatChrgArr

Wh

-

31609

Battery discharge

RO

3

U64

FIX0

1

Battery

BatDsch.BatDschArr

Wh

-

31791

Number of DC current measurement units

RO

3

U32

FIX0

1

DC Side

DcMs.AmpMsCnt

-

-

31793

DC current input

RO

3

S32

FIX3

0.001

DC Side

DcMs.Amp

A

-

32049

SSM Id for the comm. fault has occurred

RO

3

U32

FIX0

1

System communication

Operation.ComFltSSMId

-

-

32051

SMU warning code for string fault

RO

3

U32

FIX0

1

DC Side

Operation.StrFltDet.SMUWrnId

-

-

32053

Status of signal contact 1

RO

3

U32

TAGLIST

-

DC Side

Diag.SigIn1Stt

-

-

32055

Status of signal contact 2

RO

3

U32

TAGLIST

-

DC Side

Diag.SigIn2Stt

-

-

32057

String status

RO

3

U32

TAGLIST

-

DC Side

DcMs.StrgStt

-

-

32185

Internal PV reactive power limitation

RO

3

S32

FIX2

0.01

System and device control

Inverter.CurVArCtlNom

%

-

32187

Available underexcited reactive power

RO

2

U32

FIX0

1

AC Side

Measurement.Operation.CurAvailVArUnExt

var

-

32189

Available overexcited reactive power

RO

2

U32

FIX0

1

AC Side

Measurement.Operation.CurAvailVArOvExt

var

-

32191

Theoretically available system power

RO

3

U32

FIX0

1

System and device control

Operation.WAvalTheo

W

-

32193

Generation plant availability

RO

2

U32

FIX0

1

System and device control

Measurement.Operation.CurAvailPlnt

%

-

32195

External active power reduction

RO

3

U32

FIX2

0.01

System and device control

Operation.WRedEx

%

-

32197

Available underexcited reactive power

RO

2

S32

FIX2

0.01

AC Side

Measurement.Operation.CurAvailVArUnExtNom

%

-

32199

Available overexcited reactive power

RO

2

S32

FIX2

0.01

AC Side

Measurement.Operation.CurAvailVArOvExtNom

%

-

32201

Current charging power

RO

3

U64

FIX0

1

Battery

CmpBMS.GetBatChaWh

Wh

-

32205

Current discharging power

RO

3

U64

FIX0

1

Battery

CmpBMS.GetBatDschWh

Wh

-

32209

Energy released by string

RO

3

U64

FIX0

1

DC Side

DcMs.TotDcEnCntWh

Wh

-

32221

Highest measured battery temperature

RO

3

S32

TEMPERATURE

0.1

Battery

Measurement.Bat.TmpValMax

°C

-

32227

Lowest measured battery temperature

RO

3

S32

TEMPERATURE

0.1

Battery

Measurement.Bat.TmpValMin

°C

-

32233

Current battery energy content

RO

3

U32

FIX2

0.01

Battery

Bat.ChakWhStt

kWh

-

32239

End-of-charge voltage

RO

3

U32

FIX2

0.01

Battery

Measurement.Bat.ChaVolSptDmd

V

-

32245

End-of-discharge voltage

RO

3

U32

FIX2

0.01

Battery

Measurement.Bat.DschVolSptDmd

V

-

32251

Maximum charging current

RO

3

U32

FIX3

0.001

Battery

Measurement.Bat.ChaAmpSptDmd

A

-

32257

Maximum discharging current

RO

3

U32

FIX3

0.001

Battery

Measurement.Bat.DschAmpSptDmd

A

-

32263

Sum of cell voltages

RO

3

U32

FIX2

0.01

Battery

Measurement.Bat.CelVolSum

V

-

32269

Lowest measured cell voltage

RO

3

U32

FIX3

0.001

Battery

Measurement.Bat.CelVolMin

V

-

32275

Highest measured cell voltage

RO

3

U32

FIX3

0.001

Battery

Measurement.Bat.CelVolMax

V

-

32281

Temperature of dew point

RO

3

U32

TEMPERATURE

0.1

Meteorology

Env.DewPtTmp

°C

-

32283

Absolute air pressure

RO

3

U32

FIX0

1

Meteorology

Env.AirPresAbs

hPa

-

32285

Relative air pressure

RO

3

U32

FIX0

1

Meteorology

Env.AirPresRel

hPa

-

32287

Standard deviation of wind speed

RO

3

U32

FIX1

0.1

Meteorology

Env.WdSpdDv

m/s

-

32289

Standard deviation of wind direction

RO

3

U32

FIX1

0.1

Meteorology

Env.WdDirDv

°

-

32291

Quality of wind measurement

RO

3

U32

FIX0

1

Meteorology

Env.WdMsQual

%

-

32293

Absolute precipitation amount

RO

3

U32

FIX2

0.01

Meteorology

Env.PrecipRteAbs

mm

-

32295

Differential precipitation amount

RO

3

U32

FIX2

0.01

Meteorology

Env.PrecipRteDif

mm

-

32297

Precipitation intensity

RO

3

U32

FIX2

0.01

Meteorology

Env.PrecipInts

mm/h

-

32299

Precipitation type

RO

3

U32

TAGLIST

-

Meteorology

Env.PrecipTyp

-

-

32301

WMO code

RO

3

U32

FIX0

1

Meteorology

Env.WMOCode

-

-

32303

Lightning events

RO

3

U32

FIX0

1

Meteorology

Env.LgtEvt

-

-

32305

Lightning events (interval)

RO

3

U32

FIX0

1

Meteorology

Env.LgtEvtIntv

-

-

32307

External temperature sensor

RO

3

S32

TEMPERATURE

0.1

Meteorology

Env.ExSnsTmp

°C

-

32309

Operating Voltage

RO

3

U32

FIX1

0.1

Device

Operation.Vol

V

-

32311

Wind direction

RO

3

U32

FIX1

0.1

Meteorology

Env.WndDir

°

-

32313

Device temperature

RO

3

U32

FIX1

0.1

Device

Coolsys.Dev.TmpVal

°C

-

32315

Standard deviation of solar irradiation

RO

3

U32

FIX1

0.1

Meteorology

Env.TotInSolDv

W/m²

-

32331

Inclination X-axis

RO

3

S32

FIX1

0.1

Device

Operation.TiltXAx

°

-

32333

Inclination Y-axis

RO

3

S32

FIX1

0.1

Device

Operation.TiltYAx

°

-

32341

Power grid feed-in

RO

3

S32

FIX0

1

AC Side

Metering.GridMs.TotWOut

W

-

32343

Voltage setpoint

RO

3

S32

FIX2

0.01

System and device control

Operation.VolSptPu

p.u.

-

32345

Pollution degree Sensor

RO

3

U32

FIX1

0.1

Meteorology

Env.SoilDeg

%

-

32365

Transmission loss Sensor

RO

3

S32

FIX1

0.1

Meteorology

Env.TxLos

%

-

32385

Inverter status

RO

3

U32

TAGLIST

-

Status

Operation.Inverter.Health

-

-

32387

Absorbed energy

RO

3

U64

FIX0

1

AC Side

Measurement.Metering.TotWhIn

Wh

-

32391

Manual input of frequency measuring value at point of interconnection

RO

3

U32

FIX3

0.001

System and device control

PlntCtl.ManOvr.Frq.PCCMs.PlntHz

Hz

-

32393

Manual input of system voltage of line conductor L1

RO

3

U32

FIX2

0.01

System and device control

PlntCtl.ManOvr.Vol.PCCMs.PlntPhV.phsA

V

-

32395

Manual input of system voltage of line conductor L2

RO

3

U32

FIX2

0.01

System and device control

PlntCtl.ManOvr.Vol.PCCMs.PlntPhV.phsB

V

-

32397

Manual input of system voltage of line conductor L3

RO

3

U32

FIX2

0.01

System and device control

PlntCtl.ManOvr.Vol.PCCMs.PlntPhV.phsC

V

-

32399

Manual input of system voltage of line conductors L1 - L2 at point of interconnection

RO

3

U32

FIX2

0.01

System and device control

PlntCtl.ManOvr.Vol.PCCMs.PlntPhV.phsA2B

V

-

32401

Manual input of system voltage of line conductors L2 - L3 at point of interconnection

RO

3

U32

FIX2

0.01

System and device control

PlntCtl.ManOvr.Vol.PCCMs.PlntPhV.phsB2C

V

-

32403

Manual input of system voltage of line conductors L2 - L3 at point of interconnection

RO

3

U32

FIX2

0.01

System and device control

PlntCtl.ManOvr.Vol.PCCMs.PlntPhV.phsC2A

V

-

32405

Remaining duration until CP restart

RO

3

U32

HIDDEN

1

External Communication

Operation.ComRsTms

s

-

32459

UPS error, normally open contact

RO

3

U32

TAGLIST

-

Further Applications

Metering.Ups.FltCls

-

-

32461

UPS battery empty, normally open contact

RO

3

U32

TAGLIST

-

Further Applications

Metering.Ups.BatLoCls

-

-

32463

UPS battery operation, normally open contact

RO

3

U32

TAGLIST

-

Further Applications

Metering.Ups.BatModCls

-

-

32465

Heat detector monitoring, normally closed contact

RO

3

U32

TAGLIST

-

Further Applications

Metering.Trf.HeatStopOpn

-

-

32467

Heat detector monitoring, normally open contact

RO

3

U32

TAGLIST

-

Further Applications

Metering.Trf.HeatStopCls

-

-

32469

Fast stop monitoring, normally open contact

RO

3

U32

TAGLIST

-

Further Applications

Metering.Trf.FstStopCls

-

-

32471

Protective relay in the transformer field of the medium-voltage switchgear

RO

3

U32

TAGLIST

-

Further Applications

Metering.Trf.SafSw

-

-

32473

SF6 gas monitoring indicator in the medium-voltage switchgear, normally open contact

RO

3

U32

TAGLIST

-

Further Applications

Metering.Trf.PresFltCls

-

-

32475

Auxiliary contact in the transformer panel of the medium-voltage switchgear, normally closed earthing switch

RO

3

U32

TAGLIST

-

Further Applications

Metering.Trf.GndSwOpn

-

-

32477

Auxiliary contact in the transformer panel of the medium-voltage switchgear, normally open earthing switch

RO

3

U32

TAGLIST

-

Further Applications

Metering.Trf.GndSwCls

-

-

32479

Auxiliary contact in cable panel 2 of the medium-voltage switchgear, normally open earthing switch

RO

3

U32

TAGLIST

-

Further Applications

Metering.Trf.GndSw2Cls

-

-

32481

Auxiliary contact in cable panel 2 of the medium-voltage switchgear, normally closed earthing switch

RO

3

U32

TAGLIST

-

Further Applications

Metering.Trf.GndSw2Opn

-

-

32483

Auxiliary contact in cable panel 1 of the medium-voltage switchgear, normally closed earthing switch

RO

3

U32

TAGLIST

-

Further Applications

Metering.Trf.GndSw1Opn

-

-

32485

Auxiliary contact in cable panel 1 of the medium-voltage switchgear, normally open earthing switch

RO

3

U32

TAGLIST

-

Further Applications

Metering.Trf.GndSw1Cls

-

-

32487

Auxiliary contact in cable panel 2 of the medium-voltage switchgear, normally closed isolating switch

RO

3

U32

TAGLIST

-

Further Applications

Metering.Trf.DcnSw2Opn

-

-

32489

Auxiliary contact in cable panel 2 of the medium-voltage switchgear, normally open isolating switch

RO

3

U32

TAGLIST

-

Further Applications

Metering.Trf.DcnSw2Cls

-

-

32491

Auxiliary contact in cable panel 1 of the medium-voltage switchgear, normally closed isolating switch

RO

3

U32

TAGLIST

-

Further Applications

Metering.Trf.DcnSw1Opn

-

-

32493

Auxiliary contact in cable panel 1 of the medium-voltage switchgear, normally open isolating switch

RO

3

U32

TAGLIST

-

Further Applications

Metering.Trf.DcnSw1Cls

-

-

32495

Auxiliary contact in the transformer panel of the medium-voltage switchgear, normally closed isolating switch

RO

3

U32

TAGLIST

-

Further Applications

Metering.Trf.DcnSwOpn

-

-

32497

Auxiliary contact in the transformer panel of the medium-voltage switchgear, normally open isolating switch

RO

3

U32

TAGLIST

-

Further Applications

Metering.Trf.DcnSwCls

-

-

32499

Auxiliary contact in the transformer panel of the medium-voltage switchgear, normally closed circuit-breaker

RO

3

U32

TAGLIST

-

Further Applications

Metering.Trf.PwrSwOpn

-

-

32501

Auxiliary contact in the transformer panel of the medium-voltage switchgear, normally open circuit-breaker

RO

3

U32

TAGLIST

-

Further Applications

Metering.Trf.PwrSwCls

-

-

32503

Number of detected communication timeouts to external plant controller

RO

2

U32

FIX0

1

System and device control

Measurement.PlntCtl.ExPlntCtlTmOutDetCnt

-

-

32505

Number of detected communication timeouts of counter measured values

RO

2

U32

FIX0

1

System and device control

Measurement.PlntCtl.GridMsTmOutDetCnt

-

-

32507

Number of detected communication timeouts of device measured values

RO

2

U32

FIX0

1

System and device control

Measurement.PlntCtl.DevMsTmOutDetCnt

-

-

32509

Meter for amount of switches

RO

3

U32

FIX0

1

Device

Operation.Rdt.SwitchRedundancyStateCounter

-

-

33001

Standby status

RO

3

U32

TAGLIST

-

Status

Measurement.Operation.StandbyStt

4570: Wait for enable operation

4570: Wait for enable operation

33003

Operating status

RO

3

U32

TAGLIST

-

Status

Measurement.Operation.RunStt

16777213: Information not available

16777213: Information not available

33005

Status of reactive power limitation

RO

3

U32

TAGLIST

-

System and device control

Operation.VArCtl.Stt

-

-

33007

Active reactive power range

RO

2 / 3

U32

TAGLIST

-

System and device control

Measurement.Operation.VArCtl.VArModAct

4396: Reactive power mode in case of active power output
4397: Reactive power mode in case of active power draw
4398: Reactive power mode in case of zero power output

4398: Reactive power mode in case of zero power output

33009

cos φ(V), status

RO

3

U32

TAGLIST

-

System and device control

Inverter.VArModCfg.PFCtlVolCfg.Stt

-

-

33011

cos φ(V), max. number of support points

RO

3

U32

FIX0

1

System and device control

Inverter.VArModCfg.PFCtlVolCfg.Crv.NumPtMax

-

-

33013

Q(P), max. number of support points

RO

3

U32

FIX0

1

System and device control

Inverter.VArModCfg.VArCtlWCfg.Crv.NumPtMax

-

-

33015

cos φ(P), max. number of support points

RO

3

U32

FIX0

1

System and device control

Inverter.VArModCfg.PFCtlWCfg.Crv.NumPtMax

-

-

33017

Rated active power WMaxOutRtg

RO

2

S32

FIX0

1

Type Label

Parameter.Inverter.WMaxOutRtg

27000 .. 60000 W

60000 W

33019

Rated active power WMaxInRtg

RO

2 / 3

S32

FIX0

1

Type Label

Parameter.Inverter.WMaxInRtg

W

-50000 W

33021

Rated active power WMinOutRtg

RO

3

S32

FIX0

1

Type Label

Inverter.WMinOutRtg

W

-

33023

Rated active power WMinInRtg

RO

3

S32

FIX0

1

Type Label

Inverter.WMinInRtg

W

-

33025

Rated apparent power VAMaxOutRtg

RO

2 / 3

U32

FIX0

1

Type Label

Parameter.Inverter.VAMaxOutRtg

VA

50000 VA

33027

Rated apparent power VAMaxInRtg

RO

2 / 3

U32

FIX0

1

Type Label

Parameter.Inverter.VAMaxInRtg

VA

50000 VA

33029

Rated reactive power VArMaxQ1Rtg

RO

2 / 3

S32

FIX0

1

Type Label

Parameter.Inverter.VArMaxQ1Rtg

var

50000 var

33031

Rated reactive power VArMaxQ2Rtg

RO

2 / 3

S32

FIX0

1

Type Label

Parameter.Inverter.VArMaxQ2Rtg

var

50000 var

33033

Rated reactive power VArMaxQ3Rtg

RO

2 / 3

S32

FIX0

1

Type Label

Parameter.Inverter.VArMaxQ3Rtg

var

-50000 var

33035

Rated reactive power VArMaxQ4Rtg

RO

2 / 3

S32

FIX0

1

Type Label

Parameter.Inverter.VArMaxQ4Rtg

var

-50000 var

33037

Rated cos φ PFMinQ1Rtg

RO

2 / 3

U32

FIX4

0.0001

Type Label

Parameter.Inverter.PFMinQ1Rtg

-

0.4

33039

Rated cos φ PFMinQ2Rtg

RO

2 / 3

U32

FIX4

0.0001

Type Label

Parameter.Inverter.PFMinQ2Rtg

-

0.4

33041

Rated cos φ PFMinQ3Rtg

RO

2 / 3

U32

FIX4

0.0001

Type Label

Parameter.Inverter.PFMinQ3Rtg

-

0.4

33043

Rated cos φ PFMinQ4Rtg

RO

2 / 3

U32

FIX4

0.0001

Type Label

Parameter.Inverter.PFMinQ4Rtg

-

0.4

33045

Q(V), max. number of support points

RO

3

U32

FIX0

1

System and device control

Inverter.VArModCfg.VArCtlVolCfg.Crv.NumPtMax

-

-

33047

P(V), max. number of support points

RO

3

U32

FIX0

1

System and device control

Inverter.WModCfg.WCtlVolCfg.Crv.NumPtMax

-

-

34097

Fan operating time

RO

3

U64

DURATION

1

Device

Coolsys.FanCab1.AbsOpTms

s

-

34101

Fan 2 operating time

RO

3

U64

DURATION

1

Device

Coolsys.FanCab2.AbsOpTms

s

-

34105

Fan heat sink operating time

RO

3

U64

DURATION

1

Device

Coolsys.FanHs.AbsOpTms

s

-

34109

Heat sink temperature

RO

3

S32

TEMPERATURE

0.1

Device

Coolsys.Hs1.TmpVal

°C

-

34113

Internal temperature

RO

3

S32

TEMPERATURE

0.1

Device

Coolsys.Cab.TmpVal

°C

-

34121

Transformer temperature

RO

3

S32

TEMPERATURE

0.1

Device

Coolsys.Tr.TmpVal

°C

-

34125

External temperature

RO

3

S32

TEMPERATURE

0.1

Device

Coolsys.Aux1.TmpVal

°C

-

34127

Highest measured external temperature

RO

3

S32

TEMPERATURE

0.1

Device

Coolsys.Aux1.TmpValMax

°C

-

34609

Ambient temperature

RO

3

S32

TEMPERATURE

0.1

Meteorology

Env.TmpVal

°C

-

34611

Highest measured ambient temperature

RO

3

S32

TEMPERATURE

0.1

Meteorology

Env.TmpValMax

°C

-

34613

Insolation

RO

3

U32

FIX0

1

Meteorology

Env.TotInsol

W/m²

-

34615

Wind speed

RO

3

U32

FIX2

0.01

Meteorology

Env.HorWSpd

m/s

-

34617

Air humidity

RO

3

U32

FIX2

0.01

Meteorology

Env.Hmdt

%

-

34619

Atmospheric pressure

RO

3

U32

FIX2

0.01

Meteorology

Env.Pres

Pa

-

34621

Module temperature

RO

3

S32

TEMPERATURE

0.1

Meteorology

Mdul.TmpVal

°C

-

34623

Insolation on external sensor

RO

3

U32

FIX0

1

Meteorology

Env.ExInsol

W/m²

-

34625

Ambient temperature

RO

3

S32

TEMPERATURE

0.1

Meteorology

Env.TmpVal

°F

-

34627

Ambient temperature

RO

3

S32

TEMPERATURE

0.1

Meteorology

Env.TmpVal

°K

-

34629

Module temperature

RO

3

S32

TEMPERATURE

0.1

Meteorology

Mdul.TmpVal

°F

-

34631

Module temperature

RO

3

S32

TEMPERATURE

0.1

Meteorology

Mdul.TmpVal

°K

-

34633

Wind speed

RO

3

U32

FIX2

0.01

Meteorology

Env.HorWSpd

km/h

-

34635

Wind speed

RO

3

U32

FIX2

0.01

Meteorology

Env.HorWSpd

mi/h

-

34637

Analogue current input 1 (AI1)

RO

3

S32

FIX2

0.01

Device

InOut.AnInA1

mA

-

34639

Analogue current input 2 (AI2)

RO

3

S32

FIX2

0.01

Device

InOut.AnInA2

mA

-

34641

Analogue current input 3 (AI3)

RO

3

S32

FIX2

0.01

Device

InOut.AnInA3

mA

-

34643

Analogue current input 4

RO

3

S32

FIX2

0.01

Device

InOut.AnInA4

mA

-

34653

Digital input group 1 (DI1 .. DI4)

RO

3

U32

TAGLIST

-

Device

InOut.DigInSttGrp1

-

-

34655

Digital input group 2 (DI5 .. DI8)

RO

3

U32

TAGLIST

-

Device

InOut.DigInSttGrp2

-

-

34657

Status digital input

RO

3

U32

TAGLIST

-

Device

DigIn.OpMod

-

-

34659

Operating status

RO

3

U32

TAGLIST

-

Battery

Measurement.Operation.CmpBMS.OpStt

71: Interference device
303: Off
388: Operation status
1295: Standby
16777213: Information not available

388: Operation status

34661

Charge of current battery

RO

3

U64

FIX0

1

Battery

BatChrg.ActBatChrg

Wh

-

34665

Battery discharge of current battery

RO

3

U64

FIX0

1

Battery

BatDsch.ActBatDsch

Wh

-

34669

Control of battery charging via communication available

RO

3

U32

TAGLIST

-

Battery

Bat.ChaCtlComAval

-

-

34671

operations state DSP

RO

3

U32

TAGLIST

-

Device

Inverter.OpSttDSP

-

-

34695

Maximum reactive power setpoint specification

RO

2

S32

FIX2

0.01

System and device control

Measurement.Operation.VArMaxLimNom

%

-

34697

Role of the device in the redundancy system

RO

3

U32

TAGLIST

-

Device

Operation.Rdt.Role

-

-

35377

Number of events for user

RO

3

U64

FIX0

1

Status

Measurement.Operation.EvtCntUsr

-

-

35381

Number of events for installer

RO

3

U64

FIX0

1

Status

Measurement.Operation.EvtCntIstl

-

-

35385

Number of events for service

RO

3

U64

FIX0

1

Status

Operation.EvtCntSvc

-

-

35403

Standardized ramp rate of active power at the point of interconnection

RO

3

S32

FIX2

0.01

Grid connection

Metering.PCCMs.PlntWNomGraCalc

%/s

-

35405

Ramp rate of active power at the point of interconnection

RO

3

S32

FIX0

1

Grid connection

Metering.PCCMs.PlntWGraCalc

MW/min

-

35407

Number of inverters in state Run

RO

2

U32

FIX0

1

Status

Measurement.Operation.NbrRunStt

-

-

35409

Number of inverters in state Wait

RO

2

U32

FIX0

1

Status

Measurement.Operation.NbrWaitStt

-

-

35411

Number of inverters in state Stop

RO

2

U32

FIX0

1

Status

Measurement.Operation.NbrStopStt

-

-

35413

Number of inverters in state Q on Demand

RO

2

U32

FIX0

1

Status

Measurement.Operation.NbrQodStt

-

-

35415

System active power (drawn) at grid connection point

RO

2

S32

FIX0

1

Grid connection

Measurement.Metering.PCCMs.PlntCsmpW

W

-

35417

Energy drawn at the grid connection point

RO

2

U64

FIX0

1

Grid connection

Measurement.Metering.PCCMs.PlntCsmpWh

Wh

-

35421

Feed-in energy at the grid connection point

RO

2

U64

FIX0

1

Grid connection

Measurement.Metering.PCCMs.PlntWh

Wh

-

35425

Availability fast reserve for storage unit (FRS)

RO

2

U32

TAGLIST

-

Status

Measurement.Plnt.Frs.Aval

1129: Yes
1130: No

1130: No

35427

Nominal capacity of the system

RO

2

U32

FIX0

1

Status

Measurement.Plnt.CapacRtgWh

Wh

-

35429

Free capacity of the system

RO

2

U32

FIX0

1

Status

Measurement.Plnt.TotAvalCha

Wh

-

35431

Retrievable charge of the system

RO

2

U32

FIX0

1

Status

Measurement.Plnt.TotAvalDsch

Wh

-

35433

Analog voltage input

RO

3

S32

FIX3

0.001

Further Applications

InOut.AnVolIn

V

-

40001

Set PV system time

RW

3

U32

DATE_TIME

1

Device

DtTm.PlntTmSet

-

-

40003

Time zone

RW

3

U32

TAGLIST

-

Device

DtTm.TmZn

-

-

40005

Standard/Daylight saving time conversion on

RW

3

U32

TAGLIST

-

Device

DtTm.DlSvIsOn

-

-

40007

DC voltage control type

RW

3

U32

TAGLIST

-

Device

Parameter.Operation.CtrlType

46: Battery

46: Battery

40009

General operating mode

RW

2 / 3

U32

TAGLIST

-

Device

Parameter.Operation.OpMod

381: Stop
1467: Start

1467: Start

40011

Acknowledge fault

RW

2

U32

TAGLIST

-

Device

Parameter.Operation.Ackn

302: -------

302: -------

40013

Language of the user interface

RW

3

U32

TAGLIST

-

Device

CntrySettings.Lang

-

-

40015

Standardized reactive power setpoint by system control

RW

2 / 3

S16

FIX1

0.1

System and device control

Inverter.VArModCfg.VArCtlComCfg.VArNom

%

-

40016

Normalized active power limitation by PV system control

RW

2 / 3

S16

FIX0

1

System and device control

Inverter.WModCfg.WCtlComCfg.WNom

%

-

40018

Fast shut-down

RW

3

U32

TAGLIST

-

System and device control

Inverter.FstStop

-

-

40020

External measurement of the insulation resistance

RW

3

U32

TAGLIST

-

Device

Maint.ExIsoMs

-

-

40024

External cos φ setpoint specification, cos φ setpoint for active power output

RW

2 / 3

U16

FIX4

0.0001

System and device control

Inverter.VArModCfg.PFCtlComCfg.PF

-

-

40025

External cos φ setpoint specification, excitation type for active power output

RW

2 / 3

U32

TAGLIST

-

System and device control

Inverter.VArModCfg.PFCtlComCfg.PFExt

-

-

40027

reaction of excitation to changes in direction of active power

RW

3

U32

TAGLIST

-

System and device control

Inverter.VArModCfg.VArAct

-

-

40029

General operating status

RO

2 / 3

U32

TAGLIST

-

Status

Measurement.Operation.OpStt

303: Off
569: Activated
1295: Standby
1795: Bolted
16777213: Information not available

569: Activated

40031

Battery nominal capacity

RO

3

U32

FIX0

1

Battery

Bat.CapacRtg

Ah

-

40033

Max. battery temperature

RW

3

U32

TEMPERATURE

1

Battery

Bat.TmpMax

°C

-

40035

Battery type

RO

3

U32

TAGLIST

-

Battery

Bat.Typ

-

-

40037

Nominal battery voltage

RO

3

U32

FIX0

1

Battery

Bat.VRtg

V

-

40039

Battery boost charge time

RW

3

U32

DURATION

1

Battery

Cha.BstChaTmm

min

-

40041

Battery equalization charge time

RW

3

U32

DURATION

1

Battery

Cha.EqChaTmh

h

-

40043

Battery full charge time

RW

3

U32

DURATION

1

Battery

Cha.FulChaTmh

h

-

40045

Max. battery charging current

RW

3

U32

FIX3

0.001

Battery

Cha.MaxChaAmp

A

-

40047

Nominal generator current

RW

3

U32

FIX3

0.001

Generator

Gn.ARtg

A

-

40049

Automatic generator start

RW

3

U32

TAGLIST

-

Generator

Gn.AutoStr

-

-

40051

Limit battery state of charge gen. shutdown in time range

RW

3

U32

FIX0

1

Generator

GnDmdBatCha.Tm1OffLim

%

-

40053

Limit battery state of charge generator start in time range

RW

3

U32

FIX0

1

Generator

GnDmdBatCha.Tm1OnLim

%

-

40055

Manual generator control

RW

3

U32

TAGLIST

-

Generator

Gn.ManCtl

-

-

40057

Generator request via power on

RW

3

U32

TAGLIST

-

Generator

GnDmdW.IsOn

-

-

40059

Generator shutdown load limit

RW

3

U32

FIX0

1

Generator

GnDmdW.WOff

W

-

40061

Generator startup load limit

RW

3

U32

FIX0

1

Generator

GnDmdW.WOn

W

-

40063

Firmware version of the main processor

RO

3

U32

FW_VERSION

1

Device Components

Parameter.Nameplate.CmpMain.SwRev

-

03.04.80.R

40065

Firmware version of the logic component

RO

3

U32

FW_VERSION

1

Device Components

Parameter.Nameplate.CmpSigProc.SwRev

-

1.6.0.R

40067

Serial number

RO

3

U32

RAW

1

Type Label

Parameter.Nameplate.SerNum

-

-

40071

Grid forming generator

RW

3

U32

TAGLIST

-

AC Side

Operation.GriCreaSrc

-

-

40073

Lower discharge limit for self-consumption increase

RW

3

U32

FIX0

1

Device

SelfCsmp.BatChaSttMin

%

-

40075

Rise in self-consumption switched on

RW

3

U32

TAGLIST

-

Device

SelfCsmp.SelfCsmpIncIsOn

-

-

40077

Initiate device restart

RW

3

U32

TAGLIST

-

Device

Parameter.Sys.DevRstr

302: -------
1146: Execute

302: -------

40079

Battery discharge cut-off voltage

RW

3

U32

FIX2

0.01

Battery

Cha.DschStopVol

V

-

40081

Maximum battery charging current

RW

3

U32

FIX3

0.001

Battery

Cha.ChaAmpMax

A

-

40083

Maximum battery discharge current

RW

3

U32

FIX3

0.001

Battery

Cha.DschAmpMax

A

-

40085

Cell charge nominal voltage for boost charge

RW

3

U32

FIX2

0.01

Battery

Cha.BstChaVolSpt

V

-

40087

Cell charge nominal voltage for full charging

RW

3

U32

FIX2

0.01

Battery

Cha.FulChaVolSpt

V

-

40089

Cell charge nominal voltage for equalization charge

RW

3

U32

FIX2

0.01

Battery

Cha.EqChaVolSpt

V

-

40091

Cell charge nominal voltage for float charge

RW

3

U32

FIX2

0.01

Battery

Cha.TrcChaVolSpt

V

-

40093

Voltage monitoring lower minimum threshold

RW

3

U32

FIX2

0.01

Grid Monitoring

GridGuard.Cntry.VolCtl.Min

V

-

40095

Voltage monitoring upper maximum threshold

RW

3

U32

FIX2

0.01

Grid Monitoring

GridGuard.Cntry.VolCtl.Max

V

-

40097

Voltage monitoring hysteresis minimum threshold

RW

3

U32

FIX2

0.01

Grid Monitoring

GridGuard.Cntry.VolCtl.ReconMinDif

V

-

40099

Voltage monitoring hysteresis maximum threshold

RW

3

U32

FIX2

0.01

Grid Monitoring

GridGuard.Cntry.VolCtl.ReconMaxDif

V

-

40101

Frequency monitoring, lower minimum threshold

RW

3

U32

FIX2

0.01

Grid Monitoring

Parameter.GridGuard.Cntry.FrqCtl.Min

Hz

44 Hz

40103

Frequency monitoring upper maximum threshold

RW

3

U32

FIX2

0.01

Grid Monitoring

Parameter.GridGuard.Cntry.FrqCtl.Max

Hz

66 Hz

40105

Frequency monitoring hysteresis minimum threshold

RW

3

U32

FIX2

0.01

Grid Monitoring

GridGuard.Cntry.FrqCtl.ReconMinDif

Hz

-

40107

Frequency monitoring hysteresis maximum threshold

RW

3

U32

FIX2

0.01

Grid Monitoring

GridGuard.Cntry.FrqCtl.ReconMaxDif

Hz

-

40109

Country standard set

RO

3

U32

TAGLIST

-

Grid Monitoring

Measurement.GridGuard.Cntry

5347: SMA default for 50 Hz grids - stop
5348: SMA default for 60 Hz grids - stop
7508: [JP] JP50
7509: [JP] JP60
7585: [DE] VDE-AR-N4105:2018 Storage > 4.6 kVA
7590: [EU] EN50549-1:2018 LV
7591: [EU] EN50549-2:2018 MV
7595: [UK] ENA-EREC-G99/1:2018
7606: [BE] Synergrid C10/11:2019 LV Storage int. Decoup. Protection Device
7607: [BE] Synergrid C10/11:2019 LV Storage ext. Decoup. Protection Device
7608: [BE] Synergrid C10/11:2019 MV Storage int. Decoup. Protection Device
7609: [BE] Synergrid C10/11:2019 MV Storage ext. Decoup. Protection Device
7615: [AT] TOR Generator Type A V1.0:2019
7616: [AT] TOR Generator Type B V1.0:2019 System >250 kW
7625: [ES] Orden TED 749:2020 Type A Power generation systems ≤ 100 kW
7626: [ES] Orden TED 749:2020 Type B 100 kW > Power generation systems ≤ 5 MW
7634: [IT] CEI0-21:2019 Storage >11,08 kW ext. EKS
7635: [IT] CEI0-16:2019 Storage
7637: [CH] NA/EEA-NE7:2020 battery-storage system ≤ 250 kW
7639: [CH] NA/EEA-NE7:2020 battery-storage system > 250 kW
7648: [ZA] NRS 097-2-1:2017 categories A1&A2 ≤100 kVA
7649: [ZA] NRS 097-2-1:2017 category A3 > 1000 kVA
7656: [CL] NT_Ley20571 systems ≤ 100 kW
7657: [BR] ABNT NBR 16149:2013 all systems
7658: [PL] PN-EN 50549-1_2019
7660: [PL] PN-EN 50549-2_2019
7665: [AU] AS/NZS 4777.2:2020 Storage Region A
7666: [AU] AS/NZS 4777.2:2020 Storage Region B
7667: [AU] AS/NZS 4777.2:2020 Storage Region C
7668: [AU] AS/NZS 4777.2:2020 Storage Region NZ
7677: [US] UL1741/SB Cat.B-II Storage
7678: [US] UL1741/SB Cat B-III Storage
7683: [GB] Northern Ireland G99/NI systems > 16 A
7685: [DE] VDE-AR-N4110:2018 storage int. decoup. protection device
7686: [DE] VDE-AR-N4110:2018 storage ext. decoup. protection device
7689: [US] HECO SRD2.0, Cat.B III_Storage
7690: [US] CA Rule 21, Cat.B III_Storage
7699: [DE] EAAV:2024 <=30 kVA, Sp, int
7700: [DE] EAAV:2024 >30-270 kVA, Sp, ext
7703: [DE] EAAV:2024 >270-500 kVA t.13, Sp, ext
7704: [DE] EAAV:2024 >270-500 kVA t.13a, Sp, ext
7705: [Off-grid] Island mode Storage systems 50 Hz
7706: [Off-grid] Island mode Storage systems 60 Hz

7585: [DE] VDE-AR-N4105:2018 Storage > 4.6 kVA

40111

Voltage monit. gener. lower minimum threshold

RW

3

U32

FIX2

0.01

Generator

Gn.VolCtl.Min

V

-

40113

Voltage monit. gener. upper maximum threshold

RW

3

U32

FIX2

0.01

Generator

Gn.VolCtl.Max

V

-

40115

Voltage monit. gener. hysteresis min. threshold

RW

3

U32

FIX2

0.01

Generator

Gn.VolCtl.ReconMinDif

V

-

40117

Voltage monit. hysteresis generator max. threshold

RW

3

U32

FIX2

0.01

Generator

Gn.VolCtl.ReconMaxDif

V

-

40119

Frequency monit. generator lower minimum threshold

RW

3

U32

FIX2

0.01

Generator

Gn.FrqCtl.Min

Hz

-

40121

Frequency monit. generator without max. threshold

RW

3

U32

FIX2

0.01

Generator

Gn.FrqCtl.Max

Hz

-

40123

Frequency monit. gener. hysteresis min. threshold

RW

3

U32

FIX2

0.01

Generator

Gn.FrqCtl.ReconMinDif

Hz

-

40125

Freq. Monit. generator hysteresis max. threshold

RW

3

U32

FIX2

0.01

Generator

Gn.FrqCtl.ReconMaxDif

Hz

-

40127

Generator maximum reverse power

RW

3

U32

FIX0

1

Generator

Gn.WMon.RvPwrMax

W

-

40129

Generator maximum reverse power tripping time

RW

3

U32

DURATION

1

Generator

Gn.WMon.RvPwrMaxTms

s

-

40133

Grid nominal voltage

RW

3

U32

FIX0

1

Grid Monitoring

GridGuard.Cntry.VRtg

V

-

40135

Nominal frequency

RW

3

U32

FIX2

0.01

Grid Monitoring

Parameter.GridGuard.Cntry.HzRtg

Hz

50 Hz

40137

Acknowledge generator errors

RW

3

U32

TAGLIST

-

Generator

Gn.Operation.Ackn

-

-

40141

Max. start attempts after error

RW

3

U32

FIX0

1

Device

Operation.FltRstrMaxCnt

-

-

40143

Active power specif. by PV system control

RW

3

S32

FIX2

0.01

System and device control

Inverter.WModCfg.WCtlComCfg.ASpt

A

-

40145

Reactive power specif. by PV system control

RW

3

S32

FIX2

0.01

System and device control

Inverter.VArModCfg.VArCtlComCfg.ArSpt

A

-

40147

Active power limitation by PV system control

RW

3

U32

FIX2

0.01

System and device control

Inverter.WModCfg.GnCtlComCfg.AMax

A

-

40149

Active power setpoint

RW

3

S32

FIX0

1

System and device control

Inverter.WModCfg.WCtlComCfg.WSpt

W

-

40151

Eff./reac. pow. contr. via comm.

RW

3

U32

TAGLIST

-

System and device control

Inverter.WModCfg.WCtlComCfg.WCtlComAct

-

-

40153

Reactive power setpoint

RW

3

S32

FIX0

1

System and device control

Inverter.VArModCfg.VArCtlComCfg.VArSpt

var

-

40157

Automatic speedwire configuration switched on

RW

3

U32

TAGLIST

-

System communication

Parameter.Spdwr.AutoCfgIsOn

1129: Yes
1130: No

1129: Yes

40159

Speedwire IP address

RW

3

TEXT

IP4

-

System communication

Spdwr.Ip

-

-

40167

Speedwire subnet mask

RW

3

TEXT

IP4

-

System communication

Spdwr.SnetMsk

-

-

40175

Speedwire gateway address

RW

3

TEXT

IP4

-

System communication

Spdwr.GwIp

-

-

40183

Phase assignment

RW

3

U32

TAGLIST

-

AC Side

Parameter.Inverter.OutPhs

325: Phase L1
326: Phases L1, L2 and L3
327: Phase L2
329: Phase L3
402: Phases L1 and L2
403: Phases L1 and L3
404: Phases L2 and L3

326: Phases L1, L2 and L3

40185

Maximum apparent power device

RO

3

U32

FIX0

1

Device

Inverter.VALim

VA

-

40187

Battery nominal capacity

RO

2 / 3

U32

FIX0

1

Battery

Parameter.Bat.CapacRtgWh

Wh

80000 Wh

40189

Batt. manuf's max. charge capac.

RO

3

U32

FIX0

1

Battery

Parameter.BatConv.WMaxCha

W

52500 W

40191

Batt. manuf's max. disch. capac.

RO

3

U32

FIX0

1

Battery

Parameter.BatConv.WMaxDsch

W

52500 W

40193

Correction voltage, voltage increase protection

RW

3

U32

FIX3

0.001

Grid Monitoring

GridGuard.Cntry.VRefOfs

V

-

40195

Currently set apparent power limit

RW

3

U32

FIX0

1

Device

Inverter.VAMax

VA

-

40197

Current reactive power limit

RW

3

U32

FIX0

1

Device

Inverter.VArMax

var

-

40200

Operating mode of static voltage stability, configuration of static voltage stability

RW

3

U32

TAGLIST

-

System and device control

Inverter.VArModCfg.VArMod

-

-

40202

Manual reactive power setting for active power output

RW

2 / 3

S32

FIX0

1

System and device control

Parameter.Inverter.VArModCfg.VArCnstCfg.VAr

var

0 var

40204

Manual reactive power setting for active power output

RW

2 / 3

S32

FIX1

0.1

System and device control

Parameter.Inverter.VArModCfg.VArCnstCfg.VArNom

%

0 %

40206

cos φ setpoint, cos φ config., direct specif.

RW

3

S32

FIX2

0.01

System and device control

Inverter.VArModCfg.PFCnstCfg.PF

-

-

40208

cos φ excit.type, cos φ config., direct spec.

RW

3

U32

TAGLIST

-

System and device control

Inverter.VArModCfg.PFCnstCfg.PFExt

-

-

40210

Operating mode active power setting

RW

3

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WMod

303: Off
1077: Manual setting in W
1078: Manual setting in %
1079: External active power setpoint
4490: External active power setting 2
40471: External active power setting 1

1079: External active power setpoint

40212

Active power limitation P, active power configuration

RW

3

U32

FIX0

1

System and device control

Parameter.Inverter.WModCfg.WCnstCfg.W

W

50000 W

40214

Active power limitation P, active power configuration

RW

3

U32

FIX0

1

System and device control

Parameter.Inverter.WModCfg.WCnstCfg.WNom

%

100 %

40216

Operating mode of active power reduction in case of overfrequency P(f)

RW

3

U32

TAGLIST

-

System and device control

Inverter.WCtlHzModCfg.WCtlHzMod

-

-

40218

Difference between starting frequency and grid frequency, linear instantaneous power gradient configuration

RW

3

U32

FIX2

0.01

System and device control

Inverter.WCtlHzModCfg.WCtlHzCfg.HzStr

Hz

-

40220

Difference between reset frequency and grid frequency, linear instantaneous power gradient configuration

RW

3

U32

FIX2

0.01

System and device control

Inverter.WCtlHzModCfg.WCtlHzCfg.HzStop

Hz

-

40222

cos φ at start point, cos φ(P) char. config.

RW

3

U32

FIX2

0.01

System and device control

Inverter.VArModCfg.PFCtlWCfg.PFStr

-

-

40224

Excit. type at start point, cos φ(P) char. conf.

RW

3

U32

TAGLIST

-

System and device control

Inverter.VArModCfg.PFCtlWCfg.PFExtStr

-

-

40226

cos φ at end point, cos φ(P) char. config.

RW

3

U32

FIX2

0.01

System and device control

Inverter.VArModCfg.PFCtlWCfg.PFStop

-

-

40228

Excit. type at end point, cos φ(P) char. config.

RW

3

U32

TAGLIST

-

System and device control

Inverter.VArModCfg.PFCtlWCfg.PFExtStop

-

-

40230

Act. power at start point, cos φ(P) char. config.

RW

3

U32

FIX0

1

System and device control

Inverter.VArModCfg.PFCtlWCfg.WNomStr

%

-

40232

Act. power at end point, cos φ(P) char. config.

RW

3

U32

FIX0

1

System and device control

Inverter.VArModCfg.PFCtlWCfg.WNomStop

%

-

40234

Active power gradient

RW

3

U32

FIX0

1

System and device control

Inverter.WGra

%/s

-

40236

BMS operating mode

RW

3

U32

TAGLIST

-

Battery

Setpoint.PlantControl.CmpBMS.OpMod

1467: Start

1467: Start

40238

Active power gradient, linear instantaneous power gradient configuration

RW

3

U32

FIX0

1

System and device control

Inverter.WCtlHzModCfg.WCtlHzCfg.WGra

%

-

40240

Activation of stay-set indicator function, linear instantaneous power gradient configuration

RW

3

U32

TAGLIST

-

System and device control

Inverter.WCtlHzModCfg.WCtlHzCfg.HystEna

-

-

40242

P(f), active power change rate after fault end

RW

2 / 3

U32

FIX0

1

System and device control

Parameter.Inverter.WCtlHzModCfg.WCtlHzCfg.HzStopWGra

%/min

9 %/min

40244

Dynamic grid support, reactive current static

RW

3

U32

TAGLIST

-

System and device control

Parameter.Inverter.DGSModCfg.DGSFlCfg.ArGraMod

4433: Zero at dead band boundary
4434: Zero at origin

4434: Zero at origin

40246

Dynamic grid support, k-factor of react. current stat. for undervolt.

RW

3

U32

FIX2

0.01

System and device control

Parameter.Inverter.DGSModCfg.DGSFlCfg.ArGraSag

-

2

40248

Dynamic grid support, k-factor of react. current stat. for overvolt.

RW

3

U32

FIX2

0.01

System and device control

Parameter.Inverter.DGSModCfg.DGSFlCfg.ArGraSwell

-

2

40250

Dynamic grid support, operating mode

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.DGSModCfg.DGSMod

303: Off
1264: Full dynamic grid support
1265: Limited dynamic grid support

1265: Limited dynamic grid support

40252

Lower limit, voltage dead band, full dynamic grid support configuration

RW

3

S32

FIX0

1

System and device control

Inverter.DGSModCfg.DGSFlCfg.DbVolNomMin

%

-

40254

Upper limit, voltage dead band, full dynamic support configuration

RW

3

U32

FIX0

1

System and device control

Inverter.DGSModCfg.DGSFlCfg.DbVolNomMax

%

-

40256

PWM inverse voltage, dynamic grid support configuration

RW

3

U32

FIX0

1

System and device control

Inverter.DGSModCfg.PwrCirInopVolNom

%

-

40258

PWM inversion delay, dynamic grid support configuration

RW

3

U32

FIX2

0.01

System and device control

Inverter.DGSModCfg.PwrCirInopTms

s

-

40260

Characteristic curve number of the PV system control procedure P(V)

RW

3

U32

FIX0

1

System and device control

Inverter.WCtlVolModCfg.CrvNum

-

-

40262

No. of charac. pt.s to be used

RW

3

U32

FIX0

1

System and device control

Inverter.UtilCrvCfg.Crv0.NumPt

-

-

40282

X values charact. curve 1

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.CrvPt1.XVal

-

-

40306

Y values charact. curve 1

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.CrvPt1.YVal

-

-

40330

X values charact. curve 2

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.CrvPt2.XVal

-

-

40354

Y values charact. curve 2

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.CrvPt2.YVal

-

-

40378

X values charact. curve 3

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.CrvPt3.XVal

-

-

40402

Y values charact. curve 3

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.CrvPt3.YVal

-

-

40426

Frequency monitoring upper max. threshold trip. time

RW

3

U32

FIX0

1

Grid Monitoring

Parameter.GridGuard.Cntry.FrqCtl.MaxTmms

ms

100000 ms

40428

Frequency monitoring median maximum threshold

RW

3

U32

FIX2

0.01

Grid Monitoring

GridGuard.Cntry.FrqCtl.hhLim

Hz

-

40430

Frq. monitoring median max. threshold trip. time

RW

3

U32

FIX0

1

Grid Monitoring

GridGuard.Cntry.FrqCtl.hhLimTmms

ms

-

40432

Frequency monitoring, lower maximum threshold

RW

3

U32

FIX2

0.01

Grid Monitoring

Parameter.GridGuard.Cntry.FrqCtl.hLim

Hz

51.5 Hz

40434

Frequency monitoring, lower max. threshold trip. time

RW

3

U32

FIX0

1

Grid Monitoring

Parameter.GridGuard.Cntry.FrqCtl.hLimTmms

ms

100 ms

40436

Frequency monitoring upper minimum threshold

RW

3

U32

FIX2

0.01

Grid Monitoring

Parameter.GridGuard.Cntry.FrqCtl.lLim

Hz

47.5 Hz

40438

Frequency monitoring, upper min. threshold trip. time

RW

3

U32

FIX0

1

Grid Monitoring

Parameter.GridGuard.Cntry.FrqCtl.lLimTmms

ms

100 ms

40440

Frequency monitoring median minimum threshold

RW

3

U32

FIX2

0.01

Grid Monitoring

GridGuard.Cntry.FrqCtl.llLim

Hz

-

40442

Frq. monitoring median min. threshold trip. time

RW

3

U32

FIX0

1

Grid Monitoring

GridGuard.Cntry.FrqCtl.llLimTmms

ms

-

40444

Frequency monitoring, lower min. threshold trip. time

RW

3

U32

FIX0

1

Grid Monitoring

Parameter.GridGuard.Cntry.FrqCtl.MinTmms

ms

1000000 ms

40446

Voltage monitoring upper max. threshold trip. time

RW

3

U32

FIX3

0.001

Grid Monitoring

GridGuard.Cntry.VolCtl.MaxTmms

ms

-

40448

Voltage monitoring median maximum threshold

RW

3

U32

FIX2

0.01

Grid Monitoring

GridGuard.Cntry.VolCtl.hhLim

V

-

40450

Voltage monitoring, median max. threshold trip.time

RW

3

U32

FIX0

1

Grid Monitoring

Parameter.GridGuard.Cntry.VolCtl.hhLimTmms

ms

100000 ms

40452

Voltage monitoring lower maximum threshold

RW

3

U32

FIX2

0.01

Grid Monitoring

GridGuard.Cntry.VolCtl.hLim

V

-

40454

Voltage monitoring normalized lower maximum threshold

RW

3

U32

FIX3

0.001

Grid Monitoring

GridGuard.Cntry.VolCtl.hLimNom

%

-

40456

Voltage monitoring, lower max. threshold trip. time

RW

3

U32

FIX0

1

Grid Monitoring

Parameter.GridGuard.Cntry.VolCtl.hLimTmms

ms

100 ms

40458

Voltage monitoring upper minimum threshold

RW

3

U32

FIX2

0.01

Grid Monitoring

GridGuard.Cntry.VolCtl.lLim

V

-

40460

Voltage monitoring normalized upper minimum threshold

RW

3

U32

FIX3

0.001

Grid Monitoring

GridGuard.Cntry.VolCtl.lLimNom

%

-

40462

Voltage monitoring, upper min. threshold trip. time

RW

3

U32

FIX0

1

Grid Monitoring

Parameter.GridGuard.Cntry.VolCtl.lLimTmms

ms

3000 ms

40464

Voltage monitoring of median minimum threshold

RW

3

U32

FIX2

0.01

Grid Monitoring

GridGuard.Cntry.VolCtl.llLim

V

-

40466

Voltage monitoring, median min. threshold trip.time

RW

3

U32

FIX0

1

Grid Monitoring

Parameter.GridGuard.Cntry.VolCtl.llLimTmms

ms

300 ms

40468

Voltage monitoring, lower min. threshold trip. time

RW

3

U32

FIX0

1

Grid Monitoring

Parameter.GridGuard.Cntry.VolCtl.MinTmms

ms

100000 ms

40470

Island network detect. status

RW

3

U32

TAGLIST

-

Grid Monitoring

GridGuard.Cntry.Aid.Stt

-

-

40472

Grid nominal voltage

RW

2 / 3

U32

FIX0

1

AC Side

Parameter.Inverter.PlntCtl.VRef

V

400 V

40474

Reference correction voltage, PV system control

RW

3

S32

FIX0

1

AC Side

Inverter.PlntCtl.VRefOfs

V

-

40476

cos φ of start pt, cos φ(P) char. curve config

RW

3

S32

FIX2

0.01

System and device control

Inverter.VArModCfg.PFCtlWCfg.PFExtPFStr

-

-

40478

cos φ of end pt, cos φ(P) char. curve config

RW

3

S32

FIX2

0.01

System and device control

Inverter.VArModCfg.PFCtlWCfg.PFExtPFStop

-

-

40480

Nominal current of all phases

RO

3

U32

FIX3

0.001

Type Label

Parameter.Nameplate.ARtg

A

72.2 A

40482

Reactive power gradient

RW

3

U32

FIX0

1

System and device control

Inverter.VArGra

%

-

40484

Activation of active power gradient

RW

3

U32

TAGLIST

-

System and device control

Inverter.WGraEna

-

-

40486

V at zero crossing 1 of reactive power char. curve

RW

3

U32

FIX3

0.001

System and device control

Inverter.VArModCfg.VArCtlVolCfg.Vol1Nom

%

-

40488

V at zero crossing 2 of reactive power char. curve

RW

3

U32

FIX3

0.001

System and device control

Inverter.VArModCfg.VArCtlVolCfg.Vol2Nom

%

-

40490

Reactive power gradient, reactive power/voltage characteristic curve configuration Q(V)

RW

3

U32

FIX1

0.1

System and device control

Inverter.VArModCfg.VArCtlVolCfg.VArGraNom

%

-

40494

RW

3

U16

FIX4

0.0001

System and device control

Inverter.DctMrk.VArModCfg.PFCtlComCfg.PF

-

-

40495

RW

3

U32

TAGLIST

-

System and device control

Inverter.DctMrk.VArModCfg.PFCtlComCfg.PFExt

-

-

40497

MAC address

RO

3

TEXT

UTF_8

-

Type Label

Nameplate.MacId

-

-

40513

Speedwire DNS server address

RW

3

TEXT

IP4

-

System communication

Spdwr.DnsSrvIp

-

-

40521

Grid request via power switched on

RW

3

U32

TAGLIST

-

AC Side

PubGri.GriDmdW.IsOn

-

-

40523

Grid request switch-on power limit

RW

3

U32

FIX0

1

AC Side

PubGri.GriDmdW.WOn

W

-

40525

Grid request switch-off power limit

RW

3

U32

FIX0

1

AC Side

PubGri.GriDmdW.WOff

W

-

40527

Manual control of grid connection

RW

3

U32

TAGLIST

-

AC Side

PubGri.ManCtl

-

-

40529

Grid request via charge type

RW

3

U32

TAGLIST

-

AC Side

PubGri.GriDmdChaMod.ChaMod

-

-

40531

Type of AC subdistribution

RO

3

U32

TAGLIST

-

AC Side

Sys.AcTyp

-

-

40533

Manual equalization charge

RW

3

U32

TAGLIST

-

Battery

Bat.Operation.EqChaMan

-

-

40535

Generator request

RW

3

U32

TAGLIST

-

Generator

Gn.DmdMod

-

-

40537

Limit battery state of charge generator start in time range

RW

3

U32

FIX0

1

Generator

GnDmdBatCha.OnLim

%

-

40539

Limit battery state of charge gen. shutdown in time range

RW

3

U32

FIX0

1

Generator

GnDmdBatCha.OffLim

%

-

40541

Start time additional time range generator request

RW

3

U32

TIME

1

Generator

GnDmdBatCha.AddTm.StrTm

-

-

40543

End time additional time period, generator request

RW

3

U32

TIME

1

Generator

GnDmdBatCha.AddTm.StopTm

-

-

40545

Battery state of charge limit, generator start in additional time period

RW

3

U32

FIX0

1

Generator

GnDmdBatCha.AddTm.OnLim

%

-

40547

Battery state of charge limit, generator shutdown in additional time period

RW

3

U32

FIX0

1

Generator

GnDmdBatCha.AddTm.OffLim

%

-

40549

Time-controlled generator operation

RW

3

U32

TAGLIST

-

Generator

GnDmdTm.IsOn

-

-

40551

Start time for time-controlled generator op.

RW

3

U32

DATE_TIME

1

Generator

GnDmdTm.StrTm

-

-

40553

Operating time for time-controlled generator op.

RW

3

U32

DURATION

1

Generator

GnDmdTm.RunTm

s

-

40555

Repeat cycle of time-controlled generator op.

RW

3

U32

TAGLIST

-

Generator

GnDmdTm.RptCyc

-

-

40557

Generator request with set charge type

RW

3

U32

TAGLIST

-

Generator

GnDmdChaMod.ChaMod

-

-

40559

Reaction to digital input of generator request

RW

3

U32

TAGLIST

-

Generator

GnDmdDigIn.DigInRea

-

-

40561

Average time for generator request via power

RW

3

U32

DURATION

1

Generator

GnDmdW.WAvTm

s

-

40563

Average operating time of generator

RW

3

U32

DURATION

1

Generator

Operation.MinRunTm

s

-

40565

Average idle period of generator

RW

3

U32

DURATION

1

Generator

Operation.MinStopTm

s

-

40567

Cooling down time of generator

RW

3

U32

DURATION

1

Generator

Operation.CoolTm

s

-

40569

Idle period after generator fault

RW

3

U32

DURATION

1

Generator

Operation.FltStopTm

s

-

40571

Warm-up time of generator

RW

3

U32

DURATION

1

Generator

Operation.WrmTm

s

-

40573

Nominal generator frequency

RW

3

U32

FIX2

0.01

Generator

Operation.HzRtg

Hz

-

40575

Operating mode of multifunction relay

RW

3

U32

TAGLIST

-

Device

MltFncSw.OpMode

-

-

40587

Slave 1: Operating mode of multifunction relay

RW

3

U32

TAGLIST

-

Device

MltFncSw.OpModeSlv1

-

-

40599

Slave 2: Operating mode of multifunction relay

RW

3

U32

TAGLIST

-

Device

MltFncSw.OpModeSlv2

-

-

40611

Repeat cycle time of relay control for timer

RW

3

U32

TAGLIST

-

Device

MltFncSw.Tmr.TmCtlCyc

-

-

40615

Duration for which multifunction relay is activated for timer

RW

3

U32

DURATION

1

Device

MltFncSw.Tmr.TmCtlOn

s

-

40619

Start date of relay control for timer

RW

3

U32

DATE_TIME

1

Device

MltFncSw.Tmr.TmCtlStr

-

-

40623

Time-controlled inverter operation

RW

3

U32

TAGLIST

-

Device

Operation.TmCtl.IsOn

-

-

40625

Start date for time-controlled inverter operation

RW

3

U32

DATE_TIME

1

Device

Operation.TmCtl.StrTm

-

-

40627

Operating time for time-controlled inverter op.

RW

3

U32

DURATION

1

Device

Operation.TmCtl.ActTm

s

-

40629

Repeat cycle for time-controlled inverter op.

RW

3

U32

TAGLIST

-

Device

Operation.TmCtl.RptCyc

-

-

40631

Device name

RW

3

TEXT

UTF_8

-

Type Label

Parameter.Nameplate.Location

-

-

40647

Automatic updates activated

RW

3

U32

TAGLIST

-

Device

Parameter.Upd.AutoUpdIsOn

1129: Yes
1130: No

1129: Yes

40649

Time of the automatic update

RW

3

U32

TIME

1

Device

Upd.AutoUpdTm

-

-

40651

Conn. point of counter on measuring interface 1

RW

3

U32

TAGLIST

-

AC Side

Metering.MsItf1.ConnLcn

-

-

40653

Conn. point of counter on measuring interface 2

RW

3

U32

TAGLIST

-

AC Side

Metering.MsItf2.ConnLcn

-

-

40655

Conn. point of counter on measuring interface 3

RW

3

U32

TAGLIST

-

AC Side

Metering.MsItf3.ConnLcn

-

-

40657

Serial number of the counter on meas. interface 1

RW

3

U32

RAW

1

AC Side

Metering.MsItf1.SerNumEN

-

-

40659

Serial number of the counter on meas. interface 2

RW

3

U32

RAW

1

AC Side

Metering.MsItf2.SerNumEN

-

-

40661

Serial number of the counter on meas. interface 3

RW

3

U32

RAW

1

AC Side

Metering.MsItf3.SerNumEN

-

-

40663

GridGuard version

RO

3

U32

REV

1

Grid Monitoring

GridGuard.Cntry.GridGuardRev

-

-

40665

Memory card status

RO

3

U32

TAGLIST

-

Data Recording

Card.Stt

-

-

40667

Update version of the main processor

RO

3

U32

FW_VERSION

1

Device Components

Nameplate.CmpMain.SwUpdRev

-

-

40669

Start feed-in PV

RW

3

U32

TIME

1

AC Side

ExtGri.StrPvFeedTm

-

-

40671

Stop feed-in PV

RW

3

U32

TIME

1

AC Side

ExtGri.StopPvFeedTm

-

-

40673

Cut-off time until connection to external network

RW

3

U32

DURATION

1

AC Side

ExtGridMs.ProLokTm

s

-

40675

Automatic frequency control

RW

3

U32

TAGLIST

-

AC Side

Operation.AutoHzCtl

-

-

40677

Maximum current from utility grid

RW

3

U32

FIX3

0.001

AC Side

PubGri.ExtGriAMax

A

-

40679

Power feedback to utility grid allowed

RW

3

U32

TAGLIST

-

AC Side

PubGri.FeedPerm

-

-

40681

Grid request via battery state of charge switched on

RW

3

U32

TAGLIST

-

AC Side

PubGri.GriDmdBatCha.IsOn

-

-

40683

Lmt battery state of charge for connection to grid

RW

3

U32

FIX0

1

AC Side

PubGri.GriDmdBatCha.OnLim

%

-

40685

Lmt battery state of charge for disconnection from grid

RW

3

U32

FIX0

1

AC Side

PubGri.GriDmdBatCha.OffLim

%

-

40687

Start time additional time range grid request

RW

3

U32

TIME

1

AC Side

PubGri.GriDmdBatCha.AddTm.StrTm

-

-

40689

Start interval for grid request

RW

3

U32

TIME

1

AC Side

PubGri.GriDmdBatCha.AddTm.StopTm

-

-

40691

Limit battery state of charge for connect to grid in add time range

RW

3

U32

FIX0

1

AC Side

PubGri.GriDmdBatCha.AddTm.OnLim

%

-

40693

Limit battery state of charge for disconnect from grid in add time range

RW

3

U32

FIX0

1

AC Side

PubGri.GriDmdBatCha.AddTm.OffLim

%

-

40695

Energy saving mode switched on

RW

3

U32

TAGLIST

-

AC Side

SltMod.IsOn

-

-

40697

Maximum network reverse power

RW

3

U32

FIX0

1

AC Side

PubGri.PwrMon.RvPwrMax

W

-

40699

Maximum network reverse power tripping time

RW

3

U32

DURATION

1

AC Side

PubGri.PwrMon.RvPwrMaxTms

s

-

40701

Time until change-over to energy saving mode

RW

3

U32

DURATION

1

AC Side

SltMod.TrcChaSltTm

s

-

40703

Maximum duration of energy saving mode

RW

3

U32

DURATION

1

AC Side

SltMod.SltTrcChaTm

s

-

40705

Upper state of charge for reactivating feed-in

RW

3

U32

FIX0

1

System and device control

BatUsDm.ChaSttFeedAct

%

-

40707

Lower state of charge for locking feed-in

RW

3

U32

FIX0

1

System and device control

BatUsDm.ChaSttFeedIna

%

-

40709

Start time of battery protection mode level

RW

3

U32

TIME

1

Battery

ProMod.StrTm

-

-

40711

End time of battery protection mode level

RW

3

U32

TIME

1

Battery

ProMod.StopTm

-

-

40713

Battery state of charge for protection mode

RW

3

U32

FIX1

0.1

Battery

ProMod.ChaSttLim

%

-

40715

Battery switch-on limit after overtemp. shutdown

RW

3

S32

TEMPERATURE

0.1

Battery

Bat.OvTmpRstr

°C

-

40717

Line resistance of battery connection

RW

3

U32

FIX3

0.001

Battery

Bat.DcRis

Ohm

-

40719

Deep discharge protection range

RW

3

U32

FIX0

1

Battery

Parameter.BatUsDm.DschProDmLim

%

0 %

40721

End-of-discharge range

RW

3

U32

FIX0

1

Battery

Parameter.BatUsDm.DschProDmMin

%

1 %

40723

Minimum width of backup power area

RW

3

U32

FIX0

1

Battery

BatUsDm.BckDmMin

%

-

40725

Area width for conserving battery state of charge

RW

3

U32

FIX0

1

Battery

BatUsDm.SelfCsmpBrd

%

-

40727

Minimum width of self-consumption area

RW

3

U32

FIX0

1

Battery

BatUsDm.SelfCsmpBrdMin

%

-

40729

Most productive month for battery usage range

RW

3

U32

TAGLIST

-

Battery

BatUsDm.MaxYldMth

-

-

40731

Season operation active

RW

3

U32

TAGLIST

-

Battery

BatUsDm.SanModAct

-

-

40733

Voltage setpoint with deactivated battery mgmt

RW

3

U32

FIX2

0.01

Battery

Cha.BMSInaVol

V

-

40735

Cycle time full charge

RW

3

U32

DURATION

1

Battery

Cha.FulChaCycTm

s

-

40737

Cycle time equalization charge

RW

3

U32

DURATION

1

Battery

Cha.EqChaCycTm

s

-

40739

Battery temperature compensation

RW

3

S32

FIX3

0.001

Battery

Cha.TmpCpn

V/°C

-

40741

Automatic equalization charge

RW

3

U32

TAGLIST

-

Battery

Cha.EqChaAuto

-

-

40743

Type of additional DC sources

RW

3

U32

TAGLIST

-

DC Side

Sys.AuxDcTyp

-

-

40745

Limitation type of generator current

RW

3

U32

TAGLIST

-

Generator

Operation.ALimMod

-

-

40747

Sensitivity of generator failure detection

RW

3

U32

TAGLIST

-

Generator

Operation.GnFltDet

-

-

40749

Status digital input

RO

3

U32

TAGLIST

-

Device

DigIn.OpMod

-

-

40751

Inverter nominal voltage

RW

3

U32

FIX0

1

Device

Parameter.Inverter.VRtg

V

400 V

40753

Inverter nominal frequency

RW

3

U32

FIX0

1

Device

Inverter.HzRtg

Hz

-

40755

Maximum AC battery charge current

RW

3

U32

FIX3

0.001

Device

Inverter.AcChaAMax

A

-

40757

Lmt value battery state of charge for start load shedding 1

RW

3

U32

FIX0

1

Device

LodShd1.ChaStrLim

%

-

40759

Lmt value battery state of charge for stop load shedding 1

RW

3

U32

FIX0

1

Device

LodShd1.ChaStopLim

%

-

40761

Start time additional time range load shedding 1

RW

3

U32

TIME

1

Device

LodShd1.AddTm.StrTm

-

-

40763

Time load shedding 1

RW

3

U32

TIME

1

Device

LodShd1.AddTm.StopTm

-

-

40765

Limit battery state of charge for start load shedding 1 in add time range

RW

3

U32

FIX0

1

Device

LodShd1.AddTm.ChaStrLim

%

-

40767

Limit battery state of charge for stop load shedding 1 in add time range

RW

3

U32

FIX0

1

Device

LodShd1.AddTm.ChaStopLim

%

-

40769

Lmt value battery state of charge for start load shedding 2

RW

3

U32

FIX0

1

Device

LodShd2.ChaStrLim

%

-

40771

Lmt value battery state of charge for stop load shedding 2

RW

3

U32

FIX0

1

Device

LodShd2.ChaStopLim

%

-

40773

Start time additional time range load shedding 2

RW

3

U32

TIME

1

Device

LodShd2.AddTm.StrTm

-

-

40775

Time load shedding 2

RW

3

U32

TIME

1

Device

LodShd2.AddTm.StopTm

-

-

40777

Limit battery state of charge for start load shedding 2 in add time range

RW

3

U32

FIX0

1

Device

LodShd2.AddTm.ChaStrLim

%

-

40779

Limit battery state of charge for stop load shedding 2 in add time range

RW

3

U32

FIX0

1

Device

LodShd2.AddTm.ChaStopLim

%

-

40781

Temp lmt for multifunct. relay with batt comp fan

RW

3

S32

TEMPERATURE

0.1

Device

MltFncSw.BatFanTmp

°C

-

40783

Serial no. Slave1 (Phase L2)

RO

3

U32

RAW

1

Type Label

Nameplate.SerNum.Slv1

-

-

40785

Serial no. Slave2 (Phase L3)

RO

3

U32

RAW

1

Type Label

Nameplate.SerNum.Slv2

-

-

40787

Cluster behaviour when a device fails

RW

3

U32

TAGLIST

-

Device

Operation.CltFltMod

-

-

40789

Communication version

RO

3

U32

REV

1

Type Label

Nameplate.ComRev

-

-

40791

Timeout for communication error indication

RW

3

U32

FIX0

1

System and device control

Inverter.PlntCtl.IntvTmsMax

s

-

40793

Min. battery charge capac.

RW

3

U32

FIX0

1

Battery

CmpBMS.BatChaMinW

W

-

40795

Max. battery charge capac.

RW

3

U32

FIX0

1

Battery

CmpBMS.BatChaMaxW

W

-

40797

Min. battery discharge capac.

RW

3

U32

FIX0

1

Battery

CmpBMS.BatDschMinW

W

-

40799

Max. battery discharge capac.

RW

3

U32

FIX0

1

Battery

CmpBMS.BatDschMaxW

W

-

40801

Mains exch. capac. target value

RW

3

S32

FIX0

1

Battery

CmpBMS.GridWSpt

W

-

40803

Determine SOH

RW

3

U32

TAGLIST

-

Battery

CmpBMS.ActlCapacDet

-

-

40805

Energy saving mode

RW

3

U32

TAGLIST

-

System and device control

Operation.EnSavMod

-

-

40807

Hardware version of the logic component

RO

3

U32

HW_VERSION

1

Device Components

Nameplate.CmpSigProc.HwRev

-

-

40809

Revision status of the logic component

RW

3

U32

FIX0

1

Device Components

Nameplate.CmpSigProc.Rev

-

-

40811

Update version of the logic component

RO

3

U32

FW_VERSION

1

Device Components

Nameplate.CmpSigProc.SwUpdRev

-

-

40813

Serial number of the logic component

RO

3

U32

RAW

1

Device Components

Nameplate.CmpSigProc.SerNum

-

-

40815

SUSyID of the logic component

RO

3

U32

FIX0

1

Device Components

Nameplate.CmpSigProc.SusyId

-

-

40819

Firmware version of protocol converter

RO

3

U32

FW_VERSION

1

Device Components

Nameplate.CmpProtConv.SwRev

-

-

40821

Hardware version of protocol converter

RO

3

U32

HW_VERSION

1

Device Components

Nameplate.CmpProtConv.HwRev

-

-

40823

Revision status of the protocol converter

RW

3

U32

FIX0

1

Device Components

Nameplate.CmpProtConv.Rev

-

-

40825

Update version of the protocol converter

RO

3

U32

FW_VERSION

1

Device Components

Nameplate.CmpProtConv.SwUpdRev

-

-

40827

Serial number of the protocol converter

RO

3

U32

RAW

1

Device Components

Nameplate.CmpProtConv.SerNum

-

-

40829

SUSyID of protocol converter

RO

3

U32

FIX0

1

Device Components

Nameplate.CmpProtConv.SusyId

-

-

40835

Input monitoring value

RW

3

S32

FIX0

1

System and device control

Sys.ComWdIn

-

-

40837

Estimated fuel consumption since last reset

RW

3

S32

FIX1

0.1

System and device control

Gn.TotFuelCsmp

m3

-

40839

Estimated current fuel consumption

RW

3

S32

FIX1

0.1

System and device control

Gn.EstFuelCsmp

l/h

-

40841

Current generator power

RW

3

S32

FIX0

1

System and device control

Gn.TotW

W

-

40843

Currently available generator apparent power

RW

3

S32

FIX0

1

System and device control

Gn.MaxVA

VA

-

40845

Current generator reactive power

RW

3

S32

FIX0

1

System and device control

Gn.TotVAr

var

-

40847

Minimum generator power to be provided

RW

3

S32

FIX0

1

System and device control

Gn.MinW

W

-

40849

Current grid export active power

RW

3

S32

FIX0

1

System and device control

PCC.TotW

W

-

40851

Current grid export reactive power

RW

3

S32

FIX0

1

System and device control

PCC.TotVAr

var

-

40853

Reset measured values

RW

3

U32

TAGLIST

-

Device

Operation.ValRsUsr

-

-

40855

Down ramp f. charac. act. pt.

RW

3

U32

FIX1

0.1

System and device control

Inverter.UtilCrvCfg.Crv0.RmpDec

%

-

40875

Up ramp f. charac. act. pt.

RW

3

U32

FIX1

0.1

System and device control

Inverter.UtilCrvCfg.Crv0.RmpInc

%

-

40895

Adj. time for charac. act. pt.

RW

3

U32

FIX1

0.1

System and device control

Inverter.UtilCrvCfg.Crv0.CrvTms

s

-

40915

Set active power limit

RW

2 / 3

U32

FIX0

1

Device

Parameter.Inverter.WMax

W

50000 W

40917

Characteristic curve number, configuration of characteristic curve mode

RW

3

U32

FIX0

1

System and device control

Inverter.UtilCrvCfg.CrvModCfg.CrvNum

-

-

40937

Activation of the characteristic curve, configuration of characteristic curve mode

RW

3

U32

TAGLIST

-

System and device control

Inverter.UtilCrvCfg.CrvModCfg.CrvEna

-

-

40957

X-axis ref. characteristic

RW

3

U32

TAGLIST

-

System and device control

Inverter.UtilCrvCfg.Crv0.XRef

-

-

40977

Y-axis ref. characteristic

RW

3

U32

TAGLIST

-

System and device control

Inverter.UtilCrvCfg.Crv0.YRef

-

-

40997

Hysteresis voltage, dynamic grid support configuration

RW

3

U32

FIX0

1

System and device control

Inverter.DGSModCfg.HystVolNom

%

-

40999

Setpoint cos(phi) as per EEI convention

RW

3

S32

FIX4

0.0001

System and device control

Inverter.VArModCfg.PFCtlComCfg.PFEEI

-

-

41001

Maximum achievable reactive power quadrant 1

RO

3

S32

FIX0

1

Device

Inverter.VArLimQ1

var

-

41003

Maximum achievable reactive power quadrant 2

RO

3

S32

FIX0

1

Device

Inverter.VArLimQ2

var

-

41005

Maximum achievable reactive power quadrant 3

RO

3

S32

FIX0

1

Device

Inverter.VArLimQ3

var

-

41007

Maximum achievable reactive power quadrant 4

RO

3

S32

FIX0

1

Device

Inverter.VArLimQ4

var

-

41009

Minimum achievable cos(phi) quadrant 1

RO

3

S32

FIX3

0.001

Device

Inverter.PFLimQ1

-

-

41011

Minimum achievable cos(phi) quadrant 2

RO

3

S32

FIX3

0.001

Device

Inverter.PFLimQ2

-

-

41013

Minimum achievable cos(phi) quadrant 3

RO

3

S32

FIX3

0.001

Device

Inverter.PFLimQ3

-

-

41015

Minimum achievable cos(phi) quadrant 4

RO

3

S32

FIX3

0.001

Device

Inverter.PFLimQ4

-

-

41017

Adjustment time of characteristic operating point, conf. of grid integr. char. 1

RW

3

U32

FIX1

0.1

System and device control

Inverter.UtilCrvCfg.Crv.CrvTms

s

-

41019

Decrease ramp, conf. of grid integr. char. 1

RW

3

U32

FIX1

0.1

System and device control

Inverter.UtilCrvCfg.Crv.RmpDec

%

-

41021

Increase ramp, conf. of grid integr. char. 1

RW

3

U32

FIX1

0.1

System and device control

Inverter.UtilCrvCfg.Crv.RmpInc

%

-

41023

Number of points to be used, conf. of grid integr. char. 1

RW

3

U32

FIX0

1

System and device control

Inverter.UtilCrvCfg.Crv.NumPt

-

-

41025

X-axes reference, conf. of grid integration char. 1

RW

3

U32

TAGLIST

-

System and device control

Inverter.UtilCrvCfg.Crv.XRef

-

-

41027

Y-axes reference, conf. of grid integration char. 1

RW

3

U32

TAGLIST

-

System and device control

Inverter.UtilCrvCfg.Crv.YRef

-

-

41029

X value 1, conf. of grid integr. char. 1

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv.XVal1

-

-

41031

Y value 1, conf. of grid integr. char. 1

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv.YVal1

-

-

41033

X value 2, conf. of grid integr. char. 1

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv.XVal2

-

-

41035

Y value 2, conf. of grid integr. char. 1

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv.YVal2

-

-

41037

X value 3, conf. of grid integr. char. 1

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv.XVal3

-

-

41039

Y value 3, conf. of grid integr. char. 1

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv.YVal3

-

-

41041

X value 4, conf. of grid integr. char. 1

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv.XVal4

-

-

41043

Y value 4, conf. of grid integr. char. 1

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv.YVal4

-

-

41045

X value 5, conf. of grid integr. char. 1

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv.XVal5

-

-

41047

Y value 5, conf. of grid integr. char. 1

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv.YVal5

-

-

41049

X value 6, conf. of grid integr. char. 1

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv.XVal6

-

-

41051

Y value 6, conf. of grid integr. char. 1

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv.YVal6

-

-

41053

X value 7, conf. of grid integr. char. 1

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv.XVal7

-

-

41055

Y value 7, conf. of grid integr. char. 1

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv.YVal7

-

-

41057

X value 8, conf. of grid integr. char. 1

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv.XVal8

-

-

41059

Y value 8, conf. of grid integr. char. 1

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv.YVal8

-

-

41061

2nd characteristic curve number, configuration of characteristic curve mode

RW

3

U32

FIX0

1

System and device control

Inverter.UtilCrvCfg.CrvModCfg2.CrvNum

-

-

41063

2nd activation of the characteristic curve, configuration of characteristic curve mode

RW

3

U32

TAGLIST

-

System and device control

Inverter.UtilCrvCfg.CrvModCfg2.CrvEna

-

-

41065

Adjustment time of char. operating point, conf. of grid integration char. 2

RW

3

U32

FIX1

0.1

System and device control

Inverter.UtilCrvCfg.Crv2.CrvTms

s

-

41067

Decrease ramp, conf. of grid integration char. 2

RW

3

U32

FIX1

0.1

System and device control

Inverter.UtilCrvCfg.Crv2.RmpDec

%

-

41069

Increase ramp, conf. of grid integration char. 2

RW

3

U32

FIX1

0.1

System and device control

Inverter.UtilCrvCfg.Crv2.RmpInc

%

-

41071

Number of points to be used, conf. of grid integr. char. 2

RW

3

U32

FIX0

1

System and device control

Inverter.UtilCrvCfg.Crv2.NumPt

-

-

41073

Input unit, conf. of grid integration char. 2

RW

3

U32

TAGLIST

-

System and device control

Inverter.UtilCrvCfg.Crv2.XRef

-

-

41075

Output frequency, conf. of grid integration char. 2

RW

3

U32

TAGLIST

-

System and device control

Inverter.UtilCrvCfg.Crv2.YRef

-

-

41077

X value 1, conf. of grid integr. char. 2

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv2.XVal1

-

-

41079

Y value 1, conf. of grid integr. char. 2

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv2.YVal1

-

-

41081

X value 2, conf. of grid integr. char. 2

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv2.XVal2

-

-

41083

Y value 2, conf. of grid integr. char. 2

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv2.YVal2

-

-

41085

X value 3, conf. of grid integr. char. 2

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv2.XVal3

-

-

41087

Y value 3, conf. of grid integr. char. 2

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv2.YVal3

-

-

41089

X value 4, conf. of grid integr. char. 2

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv2.XVal4

-

-

41091

Y value 4, conf. of grid integr. char. 2

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv2.YVal4

-

-

41093

X value 5, conf. of grid integr. char. 2

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv2.XVal5

-

-

41095

Y value 5, conf. of grid integr. char. 2

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv2.YVal5

-

-

41097

X value 6, conf. of grid integr. char. 2

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv2.XVal6

-

-

41099

Y value 6, conf. of grid integr. char. 2

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv2.YVal6

-

-

41101

X value 7, conf. of grid integr. char. 2

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv2.XVal7

-

-

41103

Y value 7, conf. of grid integr. char. 2

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv2.YVal7

-

-

41105

X value 8, conf. of grid integr. char. 2

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv2.XVal8

-

-

41107

Y value 8, conf. of grid integr. char. 2

RW

3

S32

FIX3

0.001

System and device control

Inverter.UtilCrvCfg.Crv2.YVal8

-

-

41109

Error evaluation of the device

RW

3

U32

TAGLIST

-

Device

Diag.AlrmEna

-

-

41111

Voltage monitoring of lower minimum threshold as RMS value

RW

3

U32

FIX2

0.01

Grid Monitoring

GridGuard.Cntry.VolCtl.MinEff

V

-

41113

Voltage monitoring of lower min.threshold as RMS value for tripping time

RW

3

U32

FIX0

1

Grid Monitoring

GridGuard.Cntry.VolCtl.MinEffTmms

ms

-

41115

Voltage monitoring of upper maximum threshold as RMS value

RW

3

U32

FIX2

0.01

Grid Monitoring

GridGuard.Cntry.VolCtl.MaxEff

V

-

41117

Voltage monitoring of upper max. thresh. as RMS value for tripping time

RW

3

U32

FIX0

1

Grid Monitoring

GridGuard.Cntry.VolCtl.MaxEffTmms

ms

-

41119

Currently available generator active power

RW

3

S32

FIX0

1

System and device control

Gn.AvalW

W

-

41121

Set country standard

RW

3

U32

TAGLIST

-

Grid Monitoring

Parameter.GridGuard.CntrySet

5347: SMA default for 50 Hz grids - stop
5348: SMA default for 60 Hz grids - stop
7508: [JP] JP50
7509: [JP] JP60
7585: [DE] VDE-AR-N4105:2018 Storage > 4.6 kVA
7590: [EU] EN50549-1:2018 LV
7591: [EU] EN50549-2:2018 MV
7595: [UK] ENA-EREC-G99/1:2018
7606: [BE] Synergrid C10/11:2019 LV Storage int. Decoup. Protection Device
7607: [BE] Synergrid C10/11:2019 LV Storage ext. Decoup. Protection Device
7608: [BE] Synergrid C10/11:2019 MV Storage int. Decoup. Protection Device
7609: [BE] Synergrid C10/11:2019 MV Storage ext. Decoup. Protection Device
7615: [AT] TOR Generator Type A V1.0:2019
7616: [AT] TOR Generator Type B V1.0:2019 System >250 kW
7625: [ES] Orden TED 749:2020 Type A Power generation systems ≤ 100 kW
7626: [ES] Orden TED 749:2020 Type B 100 kW > Power generation systems ≤ 5 MW
7634: [IT] CEI0-21:2019 Storage >11,08 kW ext. EKS
7635: [IT] CEI0-16:2019 Storage
7637: [CH] NA/EEA-NE7:2020 battery-storage system ≤ 250 kW
7639: [CH] NA/EEA-NE7:2020 battery-storage system > 250 kW
7648: [ZA] NRS 097-2-1:2017 categories A1&A2 ≤100 kVA
7649: [ZA] NRS 097-2-1:2017 category A3 > 1000 kVA
7656: [CL] NT_Ley20571 systems ≤ 100 kW
7657: [BR] ABNT NBR 16149:2013 all systems
7658: [PL] PN-EN 50549-1_2019
7660: [PL] PN-EN 50549-2_2019
7665: [AU] AS/NZS 4777.2:2020 Storage Region A
7666: [AU] AS/NZS 4777.2:2020 Storage Region B
7667: [AU] AS/NZS 4777.2:2020 Storage Region C
7668: [AU] AS/NZS 4777.2:2020 Storage Region NZ
7677: [US] UL1741/SB Cat.B-II Storage
7678: [US] UL1741/SB Cat B-III Storage
7683: [GB] Northern Ireland G99/NI systems > 16 A
7685: [DE] VDE-AR-N4110:2018 storage int. decoup. protection device
7686: [DE] VDE-AR-N4110:2018 storage ext. decoup. protection device
7689: [US] HECO SRD2.0, Cat.B III_Storage
7690: [US] CA Rule 21, Cat.B III_Storage
7699: [DE] EAAV:2024 <=30 kVA, Sp, int
7700: [DE] EAAV:2024 >30-270 kVA, Sp, ext
7703: [DE] EAAV:2024 >270-500 kVA t.13, Sp, ext
7704: [DE] EAAV:2024 >270-500 kVA t.13a, Sp, ext
7705: [Off-grid] Island mode Storage systems 50 Hz
7706: [Off-grid] Island mode Storage systems 60 Hz

-

41123

Min. voltage for reconnection

RW

3

U32

FIX2

0.01

Grid Monitoring

GridGuard.Cntry.VolCtl.ReconMin

V

-

41125

Max. voltage for reconnection

RW

3

U32

FIX2

0.01

Grid Monitoring

GridGuard.Cntry.VolCtl.ReconMax

V

-

41127

Minimum switching frequency

RW

2 / 3

U32

FIX2

0.01

Grid Monitoring

Parameter.GridGuard.Cntry.FrqCtl.ReconMin

Hz

47.5 Hz

41129

Maximum switching frequency

RW

2 / 3

U32

FIX2

0.01

Grid Monitoring

Parameter.GridGuard.Cntry.FrqCtl.ReconMax

Hz

50.1 Hz

41131

Minimum voltage input

RW

3

U32

FIX2

0.01

DC Side

DcCfg.StrVol

V

-

41143

Critical voltage to end feed-in

RW

3

U32

FIX2

0.01

DC Side

DcCfg.StopVol

V

-

41155

Start delay input

RW

3

U32

FIX0

1

DC Side

Parameter.DcCfg.StrTms

s

1 s

41167

Manually set active power limitation for the entire system

RW

3

U32

FIX2

0.01

System and device control

Plnt.WMaxNom

%

-

41169

Minimum insulation resistance

RW

3

U32

FIX0

1

Grid Monitoring

Parameter.GridGuard.Cntry.LeakRisMin

Ohm

300000 Ohm

41171

Set total yield

RW

3

U32

FIX0

1

AC Side

Parameter.Metering.TotkWhOutSet

kWh

0 kWh

41173

Set total operating time at grid connection point

RW

3

U32

DURATION

1

AC Side

Parameter.Metering.TotOpTmhSet

h

0 h

41175

RW

3

S32

FIX0

1

System and device control

Inverter.WModCfg.WCtlComCfg.W.phsA

W

-

41177

RW

3

S32

FIX0

1

System and device control

Inverter.WModCfg.WCtlComCfg.W.phsB

W

-

41179

RW

3

S32

FIX0

1

System and device control

Inverter.WModCfg.WCtlComCfg.W.phsC

W

-

41181

RW

3

S32

FIX0

1

System and device control

Inverter.VArModCfg.VArCtlComCfg.VArSpt.phsA

var

-

41183

RW

3

S32

FIX0

1

System and device control

Inverter.VArModCfg.VArCtlComCfg.VArSpt.phsB

var

-

41185

RW

3

S32

FIX0

1

System and device control

Inverter.VArModCfg.VArCtlComCfg.VArSpt.phsC

var

-

41187

Source of ref. meas. for reactive/active power reduction

RW

3

U32

TAGLIST

-

System and device control

Inverter.CtlComCfg.CtlMsSrc

-

-

41189

Phased reactive/act. power specification

RW

3

U32

TAGLIST

-

System and device control

Inverter.CtlComCfg.PhsCtlMod

-

-

41191

Functions for grid/offgrid operation

RW

3

U32

TAGLIST

-

Device

Inverter.GriOffOpMod

-

-

41193

External active power setting, fallback behavior

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.CtlComCfg.WCtlCom.CtlComMssMod

2506: Values maintained
2507: Apply fallback values

2506: Values maintained

41195

External active power setting, timeout

RW

3

U32

DURATION

1

System and device control

Inverter.CtlComCfg.WCtlCom.TmsOut

s

-

41197

Fallback active power limit P in % of WMax for absent active power limit

RW

3

U32

FIX2

0.01

System and device control

Inverter.CtlComCfg.WCtlCom.FlbWNom

%

-

41199

Set active power limit at grid connection point

RW

3

U32

FIX0

1

System and device control

PCC.WMaxNom

%

-

41201

Increase rate in case of insolation change

RW

2 / 3

U32

FIX0

1

System and device control

Parameter.Inverter.WGraMpp

%/min

10000 %/min

41203

Nominal PV system power

RW

2

U32

FIX0

1

DC Side

Parameter.Plnt.DcWRtg

0 .. 4000000000 W

60000 W

41205

BMS hardware version

RO

3

U32

HW_VERSION

1

Device Components

Nameplate.CmpBMS.HwRev

-

-

41215

External active power setpoint specification, fallback value for active power setpoint specification

RW

3

S32

FIX0

1

System and device control

Inverter.WModCfg.WCtlComCfg.FlbWSpt

W

-

41217

Set active power limit at grid connection point

RW

3

U32

FIX0

1

System and device control

PCC.WMax

W

-

41219

External reactive power setting, fallback behavior

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.CtlComCfg.VArCtlCom.CtlComMssMod

2506: Values maintained
2507: Apply fallback values

2507: Apply fallback values

41221

External reactive power setting, timeout

RW

3

U32

DURATION

1

System and device control

Inverter.CtlComCfg.VArCtlCom.TmsOut

s

-

41223

External reactive power setting, fallback value

RW

2 / 3

S32

FIX2

0.01

System and device control

Parameter.Inverter.CtlComCfg.VArCtlCom.FlbVArNom

%

0 %

41225

External cos φ setting, fallback behavior

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.CtlComCfg.PFCtlCom.CtlComMssMod

2506: Values maintained
2507: Apply fallback values

2507: Apply fallback values

41227

External cos φ setting, timeout

RW

3

U32

DURATION

1

System and device control

Inverter.CtlComCfg.PFCtlCom.TmsOut

s

-

41229

External cos φ setpoint specification, fallback value of cos φ for active power output

RW

3

S32

FIX4

0.0001

System and device control

Parameter.Inverter.CtlComCfg.PFCtlCom.FlbPF

-

1

41231

Current reactive power limit at overriding required reactive power

RW

3

U32

FIX0

1

Device

Inverter.VArDmdVArMax

var

-

41233

BMS hardware version

RO

3

TEXT

UTF_8

-

Device Components

Nameplate.CmpBMS.HwRevStr

-

-

41249

Limitation of the active power consumption in %

RW

3

S32

FIX2

0.01

System and device control

Inverter.WModCfg.WCtlComCfg.WMaxInNomPrc

%

-

41251

Limitation of the active power consumption in W

RW

3

S32

FIX0

1

System and device control

Inverter.WModCfg.WCtlComCfg.WMaxIn

W

-

41257

Setpoint cos(phi) as per EEI convention

RW

3

S32

FIX4

0.0001

System and device control

Inverter.VArModCfg.PFCtlComCfg.PFEEI

-

-

41259

BMS operating mode

RW

3

U32

TAGLIST

-

Battery

Setpoint.PlantControl.CmpBMS.OpMod

1467: Start

1467: Start

41265

AFCI switched on

RW

3

U32

TAGLIST

-

Device

Inverter.AfciIsOn

-

-

41267

Heating mode

RW

3

U32

TAGLIST

-

Battery

Operation.Bat.HtMod

-

-

41269

OK to use grid power for heating mode

RW

3

U32

TAGLIST

-

Battery

Operation.Bat.GriHtMod

-

-

41277

QCG Start

RW

3

U32

TAGLIST

-

Device

Operation.Cfg.QCG

-

-

41279

QCG status

RO

3

U32

TAGLIST

-

Status

Operation.QCGStt

-

-

41281

Nominal battery voltage

RW

3

U32

TAGLIST

-

Battery

Bat.BatVTyp

-

-

41283

Nominal voltage and frequency

RW

3

U32

TAGLIST

-

Device

Inverter.AcVHzTyp

-

-

41285

Cluster configuration

RW

3

U32

TAGLIST

-

Device

Inverter.Clt.Typ

-

-

41287

Cluster system

RW

3

U32

TAGLIST

-

Device

Inverter.Clt.Sys

-

-

41289

Cluster in the multi-cluster

RW

3

U32

TAGLIST

-

Device

Inverter.Clt.CltMod

-

-

41291

Extension cluster address

RW

3

U32

FIX0

1

Device

Inverter.Clt.Addr

-

-

41293

System performance

RW

3

U32

TAGLIST

-

Device

Inverter.SysFncSel

-

-

41295

Design of the generation plant

RW

3

U32

TAGLIST

-

System and device control

GridGuard.EzaTyp

-

-

41299

Adjustment time for characteristic operating point, reactive power/voltage characteristic curve configuration Q(V)

RW

3

U32

FIX0

1

System and device control

Inverter.VArModCfg.VArCtlVolCfg.VArTms

s

-

41311

Q(V), operating mode for reference voltage adaption

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.VolRef.AutnAdjMod

303: Off
308: On
1438: Automatic

303: Off

41313

Q(V), setting time of automatic reference voltage adaption

RW

2 / 3

U32

FIX0

1

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.VolRef.AutnAdjTms

s

300 s

41315

Active power control mode

RW

2

U32

TAGLIST

-

System and device control

Parameter.Operation.PlntCtl.WCtlMod

303: Off
3352: Open loop control
3353: Closed loop control

3353: Closed loop control

41317

Reactive power control mode

RW

2

U32

TAGLIST

-

System and device control

Parameter.Operation.PlntCtl.VArCtlMod

303: Off
3352: Open loop control
3353: Closed loop control

3352: Open loop control

41319

Reactive power mode in case of active power output

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.VArModOut

303: Off
1069: Q(V) characteristic curve
1070: Q, manual setting in %
1071: Q, manual setting in var
1072: Q, external setting
1073: Q(P) characteristic curve
1074: cos φ, manual setting
1075: cos φ, external setting
1076: cos φ(P) charac. curve
4562: cos φ(V) charac. curve

303: Off

41321

Reactive power mode in case of active power draw

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.VArModIn

303: Off
1069: Q(V) characteristic curve
1070: Q, manual setting in %
1071: Q, manual setting in var
1072: Q, external setting
1073: Q(P) characteristic curve
1074: cos φ, manual setting
1075: cos φ, external setting
1076: cos φ(P) charac. curve
4562: cos φ(V) charac. curve

303: Off

41323

Reactive power for zero active power

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.VArModZerW

303: Off
1069: Q(V) characteristic curve
1070: Q, manual setting in %
1071: Q, manual setting in var
1072: Q, external setting
1073: Q(P) characteristic curve

303: Off

41325

Q(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Crv.XVal[0]

p.u.

0.93 p.u.

41327

Q(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Crv.XVal[1]

p.u.

0.93 p.u.

41329

Q(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Crv.XVal[2]

p.u.

0.93 p.u.

41331

Q(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Crv.XVal[3]

p.u.

0.93 p.u.

41333

Q(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Crv.XVal[4]

p.u.

0.93 p.u.

41335

Q(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Crv.XVal[5]

p.u.

0.93 p.u.

41337

Q(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Crv.XVal[6]

p.u.

0.93 p.u.

41339

Q(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Crv.XVal[7]

p.u.

0.93 p.u.

41341

Q(V), reactive power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Crv.YVal[0]

%

43.6 %

41343

Q(V), reactive power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Crv.YVal[1]

%

43.6 %

41345

Q(V), reactive power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Crv.YVal[2]

%

43.6 %

41347

Q(V), reactive power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Crv.YVal[3]

%

43.6 %

41349

Q(V), reactive power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Crv.YVal[4]

%

43.6 %

41351

Q(V), reactive power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Crv.YVal[5]

%

43.6 %

41353

Q(V), reactive power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Crv.YVal[6]

%

43.6 %

41355

Q(V), reactive power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Crv.YVal[7]

%

43.6 %

41357

Peak Load Shaving - charging limit

RW

3

S32

FIX0

1

System and device control

PLS.ChrgW

W

-

41359

Peak Load Shaving - discharging limit

RW

3

S32

FIX0

1

System and device control

PLS.DschW

W

-

41361

Set PV system time

RW

3

U32

DATE_TIME

1

Device

DtTm.PlntTmSet

-

-

41363

Charge energy

RW

3

U32

FIX0

1

Battery

CmpBMS.BatChaWh

Wh

-

41365

Discharge energy

RW

3

U32

FIX0

1

Battery

CmpBMS.BatDschWh

Wh

-

41367

PFMinQ1-Q4 Limit for all reactive power modes

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.PFMinEna

303: Off
308: On

303: Off

41369

Activation threshold for active power output

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.OutWNomLimAct

%

5 %

41371

Deactivation threshold for active power output

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.OutWNomLimDeAct

%

5 %

41373

Activation threshold for active power draw

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.InWNomLimAct

%

5 %

41375

Deactivation threshold for active power draw

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.InWNomLimDeAct

%

5 %

41377

Reactive power setting with voltage limitation

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.VArCfg.Crv.CrvEna

303: Off
308: On

303: Off

41383

External active power setpoint

RW

2

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlComCfg.Ena

303: Off
308: On

303: Off

41389

Difference PV system time/system time

RW

3

S32

FIX0

1

Device

DtTm.PlntTmOfsWr

s

-

41399

Data model version

RO

3

U32

FIX0

1

Type Label

Nameplate.DatMdlRev

-

-

41401

Software version

RO

3

U32

FW_VERSION

1

Type Label

Nameplate.SwRev

-

-

41403

Hardware version

RO

3

U32

HW_VERSION

1

Type Label

Nameplate.HwRev

-

-

41405

Year of factory calibration

RO

3

U32

FIX0

1

Type Label

Nameplate.ClbDt.Year

-

-

41407

Month of factory calibration

RO

3

U32

FIX0

1

Type Label

Nameplate.ClbDt.Mth

-

-

41409

Day of factory calibration

RO

3

U32

FIX0

1

Type Label

Nameplate.ClbDt.Day

-

-

41411

Interval of cyclic insulation measurement

RW

3

U32

DURATION

1

Device

Parameter.Operation.LeakRisMsDur

d

30 d

41413

Time of cyclic insulation measurement

RW

3

U32

TM_LOC

1

Device

Parameter.Operation.LeakRisMsTm

-

7200

41415

Reactive power setting with voltage limitation, voltage value

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.VArCfg.Crv.XVal[0]

p.u.

0.94 p.u.

41417

Reactive power setting with voltage limitation, voltage value

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.VArCfg.Crv.XVal[1]

p.u.

0.94 p.u.

41419

Reactive power setting with voltage limitation, voltage value

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.VArCfg.Crv.XVal[2]

p.u.

0.94 p.u.

41421

Reactive power setting with voltage limitation, voltage value

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.VArCfg.Crv.XVal[3]

p.u.

0.94 p.u.

41423

Reactive power setting with voltage limitation, reactive power value

RW

2 / 3

S32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.VArCfg.Crv.YVal[0]

%

33 %

41425

Reactive power setting with voltage limitation, reactive power value

RW

2 / 3

S32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.VArCfg.Crv.YVal[1]

%

33 %

41427

Reactive power setting with voltage limitation, reactive power value

RW

2 / 3

S32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.VArCfg.Crv.YVal[2]

%

33 %

41429

Reactive power setting with voltage limitation, reactive power value

RW

2 / 3

S32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.VArCfg.Crv.YVal[3]

%

33 %

41431

Maximum active power

RW

3

S32

FIX0

1

System and device control

Setpoint.PlantControl.Inverter.WModCfg.WCtlComCfg.WSptMax

W

-

41433

Minimum active power

RW

3

S32

FIX0

1

System and device control

Setpoint.PlantControl.Inverter.WModCfg.WCtlComCfg.WSptMin

W

-

41435

External cos φ setpoint specification, fallback value of the excitation type for active power output

RW

3

U32

TAGLIST

-

System and device control

Parameter.Inverter.CtlComCfg.PFCtlCom.FlbPFExt

1041: Overexcited
1042: Underexcited

1041: Overexcited

41437

Apply configuration of curve parameters

RW

3

U32

HIDDEN

1

System and device control

Inverter.CtlComCfg.AdptCrvReq

-

-

41439

Result of application of curve parameter configuration

RW

3

U32

HIDDEN

1

System and device control

Inverter.CtlComCfg.AdptCrvRsl

-

-

41443

Q(V), external reference voltage setting in V

RW

3

U32

FIX1

0.1

System and device control

Inverter.VArModCfg.VArCtlVolCfg.VolRef.VolRef

V

-

41445

External active power setting 2, fallback behavior

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.CtlComCfg.WCtlCom2.CtlComMssMod

2506: Values maintained
2507: Apply fallback values

2506: Values maintained

41447

External active power setting 2, fallback value of minimum active power

RW

3

S32

FIX2

0.01

System and device control

Inverter.CtlComCfg.WCtlCom2.FlbWMin

W

-

41449

External active power setting 2, fallback value of maximum active power

RW

3

S32

FIX2

0.01

System and device control

Inverter.CtlComCfg.WCtlCom2.FlbWMax

W

-

41451

External active power setting 2, timeout

RW

3

U32

DURATION

1

System and device control

Inverter.CtlComCfg.WCtlCom2.TmsOut

s

-

41453

External active power setpoint 2

RW

2

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlComCfg2.Ena

303: Off
308: On

303: Off

41455

Integral local frequency (ILF), activation via Modbus

RW

2

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlHzILFCfg.MbEna

303: Off
308: On

303: Off

41457

Dependent reference reactive power setpoint

RW

3

U32

HIDDEN

1

External Communication

Mb.SunSpec.VarModDeptRef

-

-

41459

Dependent reference Q(V) reactive power curve point

RW

3

U32

HIDDEN

1

External Communication

Mb.SunSpec.VoltVarDeptRef

-

-

41461

Dependent reference Q(P) reactive power curve point

RW

3

U32

HIDDEN

1

External Communication

Mb.SunSpec.WattVarDeptRef

-

-

41463

Total system power

RW

2

U32

FIX0

1

Grid connection

Parameter.Plnt.WRtg

0 .. 4000000000 W

60000 W

41465

Heartbeat signal for communication monitoring to external plant controller

RW

3

U32

FIX0

1

System and device control

PlntCtl.LifSignRx

-

-

41467

Max. setpoint value for active power of storage (pos. = discharge power, neg. = charge power)

RW

3

S32

FIX0

1

System and device control

Bat.WCtlCom.WSptMax

W

-

41469

Min. setpoint value for active power of storage (pos. = discharge power, neg. = charge power)

RW

3

S32

FIX0

1

System and device control

Bat.WCtlCom.WSptMin

W

-

44001

Soft start-up rate P

RW

2 / 3

U32

FIX0

1

System and device control

Parameter.Inverter.WGraConn

%/min

1200 %/min

44003

Soft start-up P

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.WGraConnEna

303: Off
308: On

308: On

44005

Soft start-up rate Q

RW

2 / 3

U32

FIX0

1

System and device control

Parameter.Inverter.VArGraConn

%/min

1200 %/min

44007

Soft start-up Q

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArGraConnEna

303: Off
308: On

303: Off

44009

Reconnection time upon restart

RW

2 / 3

U32

FIX3

0.001

Grid Monitoring

Parameter.GridGuard.Cntry.GriStrTms

s

60 s

44011

Reconnect gradient after grid fault

RW

2 / 3

U32

FIX0

1

System and device control

Parameter.Inverter.WGraRecon

%/min

9 %/min

44013

Soft start-up P after grid fault

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.WGraReconEna

303: Off
308: On

308: On

44015

Reconnection time after grid fault

RW

2 / 3

U32

FIX3

0.001

Grid Monitoring

Parameter.GridGuard.Cntry.GriFltMonTms

s

60 s

44017

Reconnection time upon short interruption

RW

2 / 3

U32

FIX3

0.001

Grid Monitoring

Parameter.GridGuard.Cntry.GriFltReConTms

s

60 s

44019

Maximum duration of a short interruption

RW

2 / 3

U32

FIX3

0.001

Grid Monitoring

Parameter.GridGuard.Cntry.GriFltTms

s

3 s

44021

Reset operating data

RW

2 / 3

U32

TAGLIST

-

Device

Parameter.Operation.ValRsIstl

973: ------

973: ------

44023

Increase rate in case of insolation change

RW

2 / 3

U32

FIX0

1

System and device control

Parameter.Inverter.WGraMpp

%/min

10000 %/min

44025

External active power setting, nominal value filter

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlComCfg.Dyn.WTmEna

303: Off
308: On

303: Off

44027

External active power setting, setting time, nominal value filter

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.WModCfg.WCtlComCfg.Dyn.WTms

s

3 s

44029

External active power setting, limitation of change rate

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlComCfg.Dyn.WGraEna

303: Off
308: On

303: Off

44031

External active power setting, increase rate

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.WModCfg.WCtlComCfg.Dyn.WGraPos

%/s

0.5 %/s

44033

External active power setting, decrease rate

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.WModCfg.WCtlComCfg.Dyn.WGraNeg

%/s

0.5 %/s

44035

External active power setting, fallback value of minimum active power

RW

3

S32

FIX2

0.01

System and device control

Inverter.CtlComCfg.WCtlCom.FlbWMin

W

-

44037

External active power setting, fallback value of maximum active power

RW

3

S32

FIX2

0.01

System and device control

Inverter.CtlComCfg.WCtlCom.FlbWMax

W

-

44039

Maximum active power

RW

3

S32

FIX2

0.01

System and device control

Inverter.WModCfg.WCtlComCfg.WSptMaxNom

%

-

44041

Minimum active power

RW

3

S32

FIX2

0.01

System and device control

Inverter.WModCfg.WCtlComCfg.WSptMinNom

%

-

44043

P(V), activation

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.Ena

303: Off
308: On

303: Off

44045

P(V), type of reference voltage

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.VRefMod

4520: Mean value of phase voltages
4521: Maximum phase voltage

4520: Mean value of phase voltages

44047

P(V), type of reference active power

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.WRefMod

4405: Maximum active power WMax
4443: Current power
4444: Potential power

4405: Maximum active power WMax

44049

P(V), number of points used

RW

2 / 3

U32

FIX0

1

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.Crv.NumPt

-

2

44051

P(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.Crv.XVal[0]

p.u.

1.1 p.u.

44053

P(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.Crv.XVal[1]

p.u.

1.1 p.u.

44055

P(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.Crv.XVal[2]

p.u.

1.1 p.u.

44057

P(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.Crv.XVal[3]

p.u.

1.1 p.u.

44059

P(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.Crv.XVal[4]

p.u.

1.1 p.u.

44061

P(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.Crv.XVal[5]

p.u.

1.1 p.u.

44063

P(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.Crv.XVal[6]

p.u.

1.1 p.u.

44065

P(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.Crv.XVal[7]

p.u.

1.1 p.u.

44067

P(V), active power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.Crv.YVal[0]

%

100 %

44069

P(V), active power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.Crv.YVal[1]

%

100 %

44071

P(V), active power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.Crv.YVal[2]

%

100 %

44073

P(V), active power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.Crv.YVal[3]

%

100 %

44075

P(V), active power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.Crv.YVal[4]

%

100 %

44077

P(V), active power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.Crv.YVal[5]

%

100 %

44079

P(V), active power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.Crv.YVal[6]

%

100 %

44081

P(V), active power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.Crv.YVal[7]

%

100 %

44083

P(V), nominal value filter

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.WTmEna

303: Off
308: On

308: On

44085

P(V), setting time, nominal value filter

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.WTms

s

3 s

44087

P(V), limitation of change rate

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.WGraEna

303: Off
308: On

303: Off

44089

P(V), increase rate

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.WGraPos

%/s

20 %/s

44091

P(V), decrease rate

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.WGraNeg

%/s

20 %/s

44093

P(V), tripping delay

RW

2 / 3

U32

DURATION

1

System and device control

Parameter.Inverter.WModCfg.WCtlVolCfg.ActTms

s

0 s

44095

Reactive power mode, reference size for reactive power setting

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.VArNomRefMod

4405: Maximum active power WMax
4406: Maximum reactive power VArMax
5335: Maximum apparent power VAMax

4405: Maximum active power WMax

44097

External cos φ setting, fallback behavior

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.CtlComCfg.PFCtlCom.CtlComMssMod

2506: Values maintained
2507: Apply fallback values

2507: Apply fallback values

44099

External cos φ setting, timeout

RW

3

U32

DURATION

1

System and device control

Inverter.CtlComCfg.PFCtlCom.TmsOut

s

-

44101

Reactive power setting, nominal value filter

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.VArCfg.Dyn.VArTmEna

303: Off
308: On

308: On

44103

Reactive power setting, setting time, nominal value filter

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.VArCfg.Dyn.VArTms

s

10 s

44105

Reactive power setting, limitation of change rate

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.VArCfg.Dyn.VArGraEna

303: Off
308: On

303: Off

44107

Reactive power setting, increase rate

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.VArCfg.Dyn.VArGraPos

%/s

1200 %/s

44109

Reactive power setting, decrease rate

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.VArCfg.Dyn.VArGraNeg

%/s

1200 %/s

44111

External cos φ setting, fallback value of cos φ in case of active power output

RW

2

U32

FIX4

0.0001

System and device control

Parameter.Inverter.CtlComCfg.PFCtlCom.FlbPFOut

0.4 .. 1

1

44113

External cos φ setting, fallback value of excitation type in case of active power output

RW

2

U32

TAGLIST

-

System and device control

Parameter.Inverter.CtlComCfg.PFCtlCom.FlbPFExtOut

1041: Overexcited
1042: Underexcited

1041: Overexcited

44115

External cos φ setting, fallback value of cos φ in case of active power draw

RW

2 / 3

U32

FIX4

0.0001

System and device control

Parameter.Inverter.CtlComCfg.PFCtlCom.FlbPFIn

-

1

44117

External cos φ setting, fallback value of excitation type in case of active power draw

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.CtlComCfg.PFCtlCom.FlbPFExtIn

1041: Overexcited
1042: Underexcited

1041: Overexcited

44119

Manual cos φ setting, cos φ nominal value in case of active power draw

RW

2 / 3

U32

FIX4

0.0001

System and device control

Parameter.Inverter.VArModCfg.PFCnstCfg.PFIn

-

1

44121

Manual cos φ setting, excitation type in case of active power draw

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.PFCnstCfg.PFExtIn

1041: Overexcited
1042: Underexcited

1042: Underexcited

44123

cos φ setting, actual value filter for active power value

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.PFCfg.Dyn.WFilTmEna

303: Off
308: On

303: Off

44125

cos φ setting, actual value filter for active power value

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.PFCfg.Dyn.WFilTms

s

1.5 s

44127

cos φ setting, nominal value filter

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.PFCfg.Dyn.VArTmEna

303: Off
308: On

308: On

44129

cos φ setting, setting time, nominal value filter

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.PFCfg.Dyn.VArTms

s

10 s

44131

cos φ setting, limitation of change rate

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.PFCfg.Dyn.VArGraEna

303: Off
308: On

303: Off

44133

cos φ setting, increase rate

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.PFCfg.Dyn.VArGraPos

%/s

1200 %/s

44135

cos φ setting, decrease rate

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.PFCfg.Dyn.VArGraNeg

%/s

1200 %/s

44141

External cos φ setting, cos φ nominal value in case of active power draw

RW

3

U32

FIX4

0.0001

System and device control

Inverter.VArModCfg.PFCtlComCfg.PFIn

0.4 .. 1

1

44143

External cos φ setting, excitation type in case of active power draw

RW

3

U32

TAGLIST

-

System and device control

Inverter.VArModCfg.PFCtlComCfg.PFExtIn

1041: Overexcited
1042: Underexcited
16777213: Information not available

1042: Underexcited

44145

Q(P), number of support points to be used

RW

2 / 3

U32

FIX0

1

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.NumPt

-

4

44147

Q(P), active power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.XVal[0]

%

50 %

44149

Q(P), active power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.XVal[1]

%

50 %

44151

Q(P), active power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.XVal[2]

%

50 %

44153

Q(P), active power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.XVal[3]

%

50 %

44155

Q(P), active power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.XVal[4]

%

50 %

44157

Q(P), active power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.XVal[5]

%

50 %

44159

Q(P), active power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.XVal[6]

%

50 %

44161

Q(P), active power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.XVal[7]

%

50 %

44163

Q(P), reactive power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.YVal[0]

%

0 %

44165

Q(P), reactive power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.YVal[1]

%

0 %

44167

Q(P), reactive power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.YVal[2]

%

0 %

44169

Q(P), reactive power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.YVal[3]

%

0 %

44171

Q(P), reactive power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.YVal[4]

%

0 %

44173

Q(P), reactive power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.YVal[5]

%

0 %

44175

Q(P), reactive power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.YVal[6]

%

0 %

44177

Q(P), reactive power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.YVal[7]

%

0 %

44179

Q(P), nominal value filter

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Dyn.VArTmEna

303: Off
308: On

308: On

44181

Q(P), setting time, nominal value filter

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Dyn.VArTms

s

10 s

44183

Q(P), limitation of change rate

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Dyn.VArGraEna

303: Off
308: On

303: Off

44185

Q(P), increase rate

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Dyn.VArGraPos

%/s

100 %/s

44187

Q(P), decrease rate

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Dyn.VArGraNeg

%/s

100 %/s

44189

Q(P), tripping delay

RW

2 / 3

U32

FIX0

1

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Dyn.ActTms

s

0 s

44191

Q(V), number of support points to be used

RW

3

U32

FIX0

1

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Crv.NumPt

-

4

44193

Q(V), fallback behavior for absent reference voltage setting

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.CtlComCfg.VArCtlVolCom.CtlComMssMod

2506: Values maintained
2507: Apply fallback values

2507: Apply fallback values

44195

Q(V), fallback of reference voltage

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.CtlComCfg.VArCtlVolCom.FlbVolRefPu

p.u.

1 p.u.

44197

Q(V), timeout for absent reference voltage setting

RW

3

U32

FIX0

1

System and device control

Inverter.CtlComCfg.VArCtlVolCom.TmsOut

s

-

44199

Q(V), nominal value filter

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Dyn.VArTmEna

303: Off
308: On

308: On

44201

Q(V), setting time, nominal value filter

RW

2

U32

FIX0

1

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Dyn.VArTms

1 .. 1000 s

10 s

44203

Q(V), limitation of change rate

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Dyn.VArGraEna

303: Off
308: On

303: Off

44205

Q(V), increase rate

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Dyn.VArGraPos

%/s

100 %/s

44207

Q(V), decrease rate

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Dyn.VArGraNeg

%/s

100 %/s

44209

Q(V), tripping delay

RW

2 / 3

U32

FIX0

1

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Dyn.ActTms

s

0 s

44211

Q(V), external reference voltage setting in p.u.

RW

3

U32

FIX3

0.001

System and device control

Inverter.VArModCfg.VArCtlVolCfg.VolRef.VolRefPu

p.u.

-

44213

cos φ(P), number of support points to be used

RW

2 / 3

U32

FIX0

1

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Crv.NumPt

-

2

44215

cos φ(P), excitation type

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Crv.PFExt[0]

1041: Overexcited
1042: Underexcited

1042: Underexcited

44217

cos φ(P), excitation type

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Crv.PFExt[1]

1041: Overexcited
1042: Underexcited

1042: Underexcited

44219

cos φ(P), excitation type

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Crv.PFExt[2]

1041: Overexcited
1042: Underexcited

1042: Underexcited

44221

cos φ(P), excitation type

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Crv.PFExt[3]

1041: Overexcited
1042: Underexcited

1042: Underexcited

44223

cos φ(P), cos φ nominal value

RW

2 / 3

U32

FIX4

0.0001

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Crv.PF[0]

-

1

44225

cos φ(P), cos φ nominal value

RW

2 / 3

U32

FIX4

0.0001

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Crv.PF[1]

-

1

44227

cos φ(P), cos φ nominal value

RW

2 / 3

U32

FIX4

0.0001

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Crv.PF[2]

-

1

44229

cos φ(P), cos φ nominal value

RW

2 / 3

U32

FIX4

0.0001

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Crv.PF[3]

-

1

44231

cos φ(P), active power

RW

2 / 3

S32

FIX0

1

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Crv.WNom[0]

%

50 %

44233

cos φ(P), active power

RW

2 / 3

S32

FIX0

1

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Crv.WNom[1]

%

50 %

44235

cos φ(P), active power

RW

2 / 3

S32

FIX0

1

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Crv.WNom[2]

%

50 %

44237

cos φ(P), active power

RW

2 / 3

S32

FIX0

1

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Crv.WNom[3]

%

50 %

44239

cos φ(P), actual value filter for active power measured value

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Dyn.WFilTmEna

303: Off
308: On

303: Off

44241

cos φ(P), setting time, actual value filter

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Dyn.WFilTms

s

1.5 s

44243

cos φ(P), nominal value filter

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Dyn.VArTmEna

303: Off
308: On

308: On

44245

cos φ(P), setting time, nominal value filter

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Dyn.VArTms

s

10 s

44247

cos φ(P), limitation of change rate

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Dyn.VArGraEna

303: Off
308: On

303: Off

44249

cos φ(P), increase rate

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Dyn.VArGraPos

%/s

1200 %/s

44251

cos φ(P), decrease rate

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Dyn.VArGraNeg

%/s

1200 %/s

44253

cos φ(P), tripping delay

RW

2 / 3

U32

FIX0

1

System and device control

Parameter.Inverter.VArModCfg.PFCtlWCfg.Dyn.ActTms

s

0 s

44255

cos φ(V), number of support points used

RW

2 / 3

U32

FIX0

1

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Crv.NumPt

-

4

44257

cos φ(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Crv.VolPu[0]

p.u.

0.94 p.u.

44259

cos φ(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Crv.VolPu[1]

p.u.

0.94 p.u.

44261

cos φ(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Crv.VolPu[2]

p.u.

0.94 p.u.

44263

cos φ(V), voltage value

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Crv.VolPu[3]

p.u.

0.94 p.u.

44265

cos φ(V), excitation type

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Crv.PFExt[0]

1041: Overexcited
1042: Underexcited

1041: Overexcited

44267

cos φ(V), excitation type

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Crv.PFExt[1]

1041: Overexcited
1042: Underexcited

1041: Overexcited

44269

cos φ(V), excitation type

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Crv.PFExt[2]

1041: Overexcited
1042: Underexcited

1041: Overexcited

44271

cos φ(V), excitation type

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Crv.PFExt[3]

1041: Overexcited
1042: Underexcited

1041: Overexcited

44273

cos φ(V), cos φ nominal value

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Crv.PF[0]

-

0.8

44275

cos φ(V), cos φ nominal value

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Crv.PF[1]

-

0.8

44277

cos φ(V), cos φ nominal value

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Crv.PF[2]

-

0.8

44279

cos φ(V), cos φ nominal value

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Crv.PF[3]

-

0.8

44281

cos φ(V), actual value filter for active power measured value

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Dyn.WFilTmEna

303: Off
308: On

303: Off

44283

cos φ(V), setting time, actual value filter

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Dyn.WFilTms

s

1.5 s

44285

cos φ(V), nominal value filter

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Dyn.VArTmEna

303: Off
308: On

308: On

44287

cos φ(P), setting time, nominal value filter

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Dyn.VArTms

s

10 s

44289

cos φ(P), limitation of change rate

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Dyn.VArGraEna

303: Off
308: On

303: Off

44291

cos φ(V), increase rate

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Dyn.VArGraPos

%/s

1200 %/s

44293

cos φ(V), decrease rate

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Dyn.VArGraNeg

%/s

1200 %/s

44295

cos φ(V), tripping delay

RW

2 / 3

U32

DURATION

1

System and device control

Parameter.Inverter.VArModCfg.PFCtlVolCfg.Dyn.ActTms

s

0 s

44297

Voltage monitoring, upper maximum threshold

RW

3

U32

FIX3

0.001

Grid Monitoring

Parameter.GridGuard.Cntry.VolCtl.MaxPu

p.u.

2 p.u.

44299

Voltage monitoring, median maximum threshold

RW

3

U32

FIX3

0.001

Grid Monitoring

Parameter.GridGuard.Cntry.VolCtl.hhLimPu

p.u.

2 p.u.

44301

Voltage monitoring, lower maximum threshold

RW

3

U32

FIX3

0.001

Grid Monitoring

Parameter.GridGuard.Cntry.VolCtl.hLimPu

p.u.

1.25 p.u.

44303

Voltage monitoring, upper max. threshold trip. time

RW

3

U32

FIX0

1

Grid Monitoring

Parameter.GridGuard.Cntry.VolCtl.MaxPuTmms

ms

100000 ms

44305

Voltage monitoring, lower minimum threshold

RW

3

U32

FIX3

0.001

Grid Monitoring

Parameter.GridGuard.Cntry.VolCtl.MinPu

p.u.

0.2 p.u.

44307

Voltage monitoring, median minimum threshold

RW

3

U32

FIX3

0.001

Grid Monitoring

Parameter.GridGuard.Cntry.VolCtl.llLimPu

p.u.

0.45 p.u.

44309

Voltage monitoring, upper minimum threshold

RW

3

U32

FIX3

0.001

Grid Monitoring

Parameter.GridGuard.Cntry.VolCtl.lLimPu

p.u.

0.8 p.u.

44311

Max. voltage for reconnection

RW

2 / 3

U32

FIX3

0.001

Grid Monitoring

Parameter.GridGuard.Cntry.VolCtl.ReconMaxPu

p.u.

1.1 p.u.

44313

Min. voltage for reconnection

RW

2 / 3

U32

FIX3

0.001

Grid Monitoring

Parameter.GridGuard.Cntry.VolCtl.ReconMinPu

p.u.

0.85 p.u.

44315

Voltage monitoring, peak voltage threshold

RW

3

U32

FIX3

0.001

Grid Monitoring

Parameter.GridGuard.Cntry.VolCtl.MaxPeakPu

p.u.

1.78 p.u.

44317

Voltage monitoring, peak voltage threshold tripping time

RW

3

U32

FIX3

0.001

Grid Monitoring

Parameter.GridGuard.Cntry.VolCtl.MaxPeakTmms

ms

0.312 ms

44319

Dynamic grid support, overvoltage threshold for zero current

RW

3

U32

FIX2

0.01

System and device control

Parameter.Inverter.DGSModCfg.ZerCurOvVolPu

p.u.

1.15 p.u.

44321

Dynamic grid support, undervoltage threshold for zero current

RW

3

U32

FIX2

0.01

System and device control

Parameter.Inverter.DGSModCfg.ZerCurUnVolPu

p.u.

0.8 p.u.

44323

Dynamic grid support, hysteresis voltage

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.DGSModCfg.HystVolPu

p.u.

0.05 p.u.

44325

Dynamic grid support, averaging for reactive current static

RW

3

U32

TAGLIST

-

System and device control

Parameter.Inverter.DGSModCfg.DGSFlCfg.VRefArMod

303: Off
308: On

308: On

44327

Dynamic grid support, overvoltage threshold for reactive current

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.DGSModCfg.DGSFlCfg.DbVMaxPu

p.u.

1.1 p.u.

44329

Dynamic grid support, undervoltage threshold for reactive current

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.DGSModCfg.DGSFlCfg.DbVMinPu

p.u.

0.9 p.u.

44331

Dynamic grid support, voltage leap height

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.DGSModCfg.DGSFlCfg.StepVolPu

p.u.

0.03 p.u.

44333

P(f) characteristic curve

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.WCtlHzModCfg.Ena

303: Off
308: On

308: On

44335

P(f) reference value for active power in case of overfrequency

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.WCtlHzModCfg.RefModOv

4354: Maximum active power export
4443: Current power
4444: Potential power
5249: Potential power with characteristic curve break

4354: Maximum active power export

44337

P(f), reference value for active power for underfrequency

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.WCtlHzModCfg.RefModUn

4354: Maximum active power export
4443: Current power
4444: Potential power
5249: Potential power with characteristic curve break

4354: Maximum active power export

44339

P(f), setting time

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.WCtlHzModCfg.WTms

s

0.5 s

44341

P(f), hysteresis in case of overfrequency

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.WCtlHzModCfg.WCtlHzCfg.HystEnaOv

303: Off
308: On

303: Off

44343

P(f), hysteresis in case of underfrequency

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.WCtlHzModCfg.WCtlHzCfg.HystEnaUn

303: Off
308: On

303: Off

44345

P(f), buckling overfrequency

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.WCtlHzModCfg.WCtlHzCfg.HzOv[0]

Hz

50.2 Hz

44347

P(f), buckling overfrequency

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.WCtlHzModCfg.WCtlHzCfg.HzOv[1]

Hz

50.2 Hz

44349

P(f), buckling overfrequency

RW

2 / 3

U32

FIX3

0.001

System and device control

Parameter.Inverter.WCtlHzModCfg.WCtlHzCfg.HzOv[2]

Hz

50.2 Hz

44351

P(f), active power change per Hz in case of overfrequency

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.WCtlHzModCfg.WCtlHzCfg.HzOvGra[0]

%

-40 %

44353

P(f), active power change per Hz in case of overfrequency

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.WCtlHzModCfg.WCtlHzCfg.HzOvGra[1]

%

-40 %

44355

P(f), active power change per Hz in case of overfrequency

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.WCtlHzModCfg.WCtlHzCfg.HzOvGra[2]

%

-40 %

44357

P(f), reset underfrequency

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.WCtlHzModCfg.WCtlHzCfg.HzOvStop

Hz

50.2 Hz

44359

P(f), buckling underfrequency

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.WCtlHzModCfg.WCtlHzCfg.HzUn[0]

Hz

49.8 Hz

44361

P(f), buckling underfrequency

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.WCtlHzModCfg.WCtlHzCfg.HzUn[1]

Hz

49.8 Hz

44363

P(f), buckling underfrequency

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.WCtlHzModCfg.WCtlHzCfg.HzUn[2]

Hz

49.8 Hz

44365

P(f), active power change per Hz in case of underfrequency

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.WCtlHzModCfg.WCtlHzCfg.HzUnGra[0]

%

-100 %

44367

P(f), active power change per Hz in case of underfrequency

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.WCtlHzModCfg.WCtlHzCfg.HzUnGra[1]

%

-100 %

44369

P(f), active power change per Hz in case of underfrequency

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.WCtlHzModCfg.WCtlHzCfg.HzUnGra[2]

%

-100 %

44371

P(f), reset underfrequency

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.WCtlHzModCfg.WCtlHzCfg.HzUnStop

Hz

49.8 Hz

44373

P(f), tripping delay

RW

2 / 3

U32

FIX0

1

System and device control

Parameter.Inverter.WCtlHzModCfg.WCtlHzCfg.WCtlTmms

ms

0 ms

44375

P(f), lag time

RW

2 / 3

U32

DURATION

1

System and device control

Parameter.Inverter.WCtlHzModCfg.WCtlHzCfg.HzStopWGraTms

s

0 s

44377

Islanding detection, status of frequency monitor

RW

3

U32

TAGLIST

-

Grid Monitoring

Parameter.GridGuard.Cntry.Aid.HzMon.Stt

303: Off
308: On

308: On

44379

Islanding detection, tripping time of the frequency monitor

RW

3

U32

FIX0

1

Grid Monitoring

Parameter.GridGuard.Cntry.Aid.HzMon.HzMonTmms

ms

5000 ms

44381

Nominal active power WMaxOut

RW

2

S32

FIX0

1

AC Side

Parameter.Inverter.WMaxOut

0 .. 60000 W

60000 W

44383

Nominal active power WMaxIn

RW

2 / 3

S32

FIX0

1

AC Side

Parameter.Inverter.WMaxIn

W

-50000 W

44385

Nominal active power WMinOut

RW

3

S32

FIX0

1

AC Side

Inverter.WMinOut

W

-

44387

Nominal active power WMinIn

RW

3

S32

FIX0

1

AC Side

Inverter.WMinIn

W

-

44389

Nominal apparent power VAMaxOut

RW

2 / 3

U32

FIX0

1

AC Side

Parameter.Inverter.VAMaxOut

VA

50000 VA

44391

Nominal apparent power VAMaxIn

RW

2 / 3

U32

FIX0

1

AC Side

Parameter.Inverter.VAMaxIn

VA

50000 VA

44393

Nominal reactive power VArMaxQ1

RW

2 / 3

S32

FIX0

1

AC Side

Parameter.Inverter.VArMaxQ1

var

49500 var

44395

Nominal reactive power VArMaxQ2

RW

2 / 3

S32

FIX0

1

AC Side

Parameter.Inverter.VArMaxQ2

var

49500 var

44397

Nominal reactive power VArMaxQ3

RW

2 / 3

S32

FIX0

1

AC Side

Parameter.Inverter.VArMaxQ3

var

-49500 var

44399

Nominal reactive power VArMaxQ4

RW

2 / 3

S32

FIX0

1

AC Side

Parameter.Inverter.VArMaxQ4

var

-49500 var

44401

Nominal reactive power VArMaxZerWQ1

RW

2 / 3

S32

FIX0

1

AC Side

Parameter.Inverter.VArMaxZerWQ1

var

50000 var

44403

Nominal reactive power VArMaxZerWQ2

RW

2 / 3

S32

FIX0

1

AC Side

Parameter.Inverter.VArMaxZerWQ2

var

50000 var

44405

Nominal reactive power VArMaxZerWQ3

RW

2 / 3

S32

FIX0

1

AC Side

Parameter.Inverter.VArMaxZerWQ3

var

-50000 var

44407

Nominal reactive power VArMaxZerWQ4

RW

2 / 3

S32

FIX0

1

AC Side

Parameter.Inverter.VArMaxZerWQ4

var

-50000 var

44409

Nominal cos φ PFMinQ1

RW

2 / 3

U32

FIX4

0.0001

AC Side

Parameter.Inverter.PFMinQ1

-

0.4

44411

Nominal cos φ PFMinQ2

RW

2 / 3

U32

FIX4

0.0001

AC Side

Parameter.Inverter.PFMinQ2

-

0.4

44413

Nominal cos φ PFMinQ3

RW

2 / 3

U32

FIX4

0.0001

AC Side

Parameter.Inverter.PFMinQ3

-

0.4

44415

Nominal cos φ PFMinQ4

RW

2 / 3

U32

FIX4

0.0001

AC Side

Parameter.Inverter.PFMinQ4

-

0.4

44417

Islanding detection, status of the unbalance detection

RW

3

U32

TAGLIST

-

Grid Monitoring

Parameter.GridGuard.Cntry.Aid.AsymDet.Stt

303: Off
308: On

303: Off

44419

Islanding detection, permissible grid unbalance

RW

3

U32

FIX0

1

Grid Monitoring

Parameter.GridGuard.Cntry.Aid.AsymDet.AsymMax

%

50 %

44421

Islanding detection, tripping time of the unbalance detection

RW

3

U32

FIX0

1

Grid Monitoring

Parameter.GridGuard.Cntry.Aid.AsymDet.AsymMaxTmms

ms

5000 ms

44423

Energy saving mode

RW

3

U32

TAGLIST

-

System and device control

Operation.EnSavMod

-

-

44425

Active power setpoint

RW

3

S32

FIX0

1

System and device control

Inverter.WModCfg.WCtlComCfg.WSpt

W

-

44427

Eff./reac. pow. contr. via comm.

RW

3

U32

TAGLIST

-

System and device control

Inverter.WModCfg.WCtlComCfg.WCtlComAct

-

-

44431

Min. battery charge capac.

RW

3

U32

FIX0

1

Battery

CmpBMS.BatChaMinW

W

-

44433

Max. battery charge capac.

RW

3

U32

FIX0

1

Battery

CmpBMS.BatChaMaxW

W

-

44435

Min. battery discharge capac.

RW

3

U32

FIX0

1

Battery

CmpBMS.BatDschMinW

W

-

44437

Max. battery discharge capac.

RW

3

U32

FIX0

1

Battery

CmpBMS.BatDschMaxW

W

-

44439

Mains exch. capac. target value

RW

3

S32

FIX0

1

Battery

CmpBMS.GridWSpt

W

-

44441

Determine SOH

RW

3

U32

TAGLIST

-

Battery

CmpBMS.ActlCapacDet

-

-

44443

Priority compared to local charact. curves

RW

3

U32

TAGLIST

-

System and device control

Inverter.WModCfg.WCtlComCfg.WSptMaxPrioCat

-

-

44445

Priority compared to local charact. curves

RW

3

U32

TAGLIST

-

System and device control

Inverter.WModCfg.WCtlComCfg.WSptMinPrioCat

-

-

44447

AID rate of rise

RW

3

U32

TAGLIST

-

Grid Monitoring

GridGuard.Cntry.Aid.Steepn

-

-

44449

Battery maximum active power

RW

3

S32

FIX2

0.01

System and device control

Bat.WCtlCom.WSptMaxNom

0 .. 100 %

-

44451

Battery minimum active power

RW

3

S32

FIX2

0.01

System and device control

Bat.WCtlCom.WSptMinNom

0 .. 100 %

-

44453

External cos φ setting, cos φ nominal value in case of active power output

RW

3

U32

FIX4

0.0001

System and device control

Inverter.VArModCfg.PFCtlComCfg.PFOut

-

-

44455

External cos φ setting, excitation type in case of active power output

RW

3

U32

TAGLIST

-

System and device control

Inverter.VArModCfg.PFCtlComCfg.PFExtOut

-

-

44457

Active power setpoint for battery system

RW

3

U32

FIX3

0.001

System and device control

Bat.WCtlCom.WSptNomPrc

%

-

44461

External active power setting 2, nominal value filter

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlComCfg2.Dyn.WTmEna

303: Off
308: On

303: Off

44463

External active power setting 2, limitation of change rate

RW

2 / 3

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlComCfg2.Dyn.WGraEna

303: Off
308: On

303: Off

44465

External active power setting 2, increase rate

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.WModCfg.WCtlComCfg2.Dyn.WGraPos

%/s

0.5 %/s

44467

External active power setting 2, decrease rate

RW

2 / 3

U32

FIX2

0.01

System and device control

Parameter.Inverter.WModCfg.WCtlComCfg2.Dyn.WGraNeg

%/s

0.5 %/s

44469

Q(P), active power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.XVal[8]

%

50 %

44471

Q(P), active power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.XVal[9]

%

50 %

44473

Q(P), reactive power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.YVal[8]

%

0 %

44475

Q(P), reactive power value

RW

2 / 3

S32

FIX3

0.001

System and device control

Parameter.Inverter.VArModCfg.VArCtlWCfg.Crv.YVal[9]

%

0 %

44477

Q(V), response time for setpoint filter

RW

3

U32

FIX2

0.01

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Dyn.VArTmsPrc

s

10 s

44479

Frequency containment reserve (FCR)

RW

2

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Ena

303: Off
308: On

303: Off

44481

Peak load limit: discharging limiting value when the state of charge is low

RW

3

S32

FIX1

0.1

DC Side

PLS.CsmpChaSttLimLo

kW

-

44483

Peak load limit: charging limiting value when the state of charge is low

RW

3

S32

FIX1

0.1

DC Side

PLS.FeedLimChaSttLo

kW

-

44485

Peak load limit: state of charge limit for switching the parameter sets

RW

3

U32

FIX1

0.1

DC Side

PLS.ChaSttThold

%

-

44487

Peak load limit: discharging limiting value when the state of charge is high

RW

3

S32

FIX1

0.1

DC Side

PLS.CsmpChaSttLimHi

kW

-

44489

Peak load limit: charging limiting value when the state of charge is high

RW

3

S32

FIX1

0.1

DC Side

PLS.FeedLimChaSttHi

kW

-

44491

Hysteresis charge/discharge limits switchover STPS-60

RW

3

U32

FIX1

0.1

AC Side

PLS.SocTholdHyst

%

-

44493

Active power limitation by PV system control

RW

3

S32

FIX0

1

System and device control

Inverter.WModCfg.WCtlComCfg.W

0 .. 60000 W

-

44495

Maximum connection voltage after restart

RW

3

U32

FIX3

0.001

Grid Monitoring

Parameter.GridGuard.Cntry.VolCtl.ConnMaxPu

p.u.

1.1 p.u.

44497

Minimum connection voltage after restart

RW

3

U32

FIX3

0.001

Grid Monitoring

Parameter.GridGuard.Cntry.VolCtl.ConnMinPu

p.u.

0.85 p.u.

44499

Maximum connection frequency after restart

RW

3

U32

FIX2

0.01

Grid Monitoring

Parameter.GridGuard.Cntry.FrqCtl.ConnMax

Hz

50.1 Hz

44501

Minimum connection frequency after restart

RW

3

U32

FIX2

0.01

Grid Monitoring

Parameter.GridGuard.Cntry.FrqCtl.ConnMin

Hz

47.5 Hz

44503

Maximum connection frequency after overfrequency disconnection

RW

3

U32

FIX2

0.01

Grid Monitoring

Parameter.GridGuard.Cntry.FrqCtl.ReconMaxFrqMax

Hz

50.1 Hz

44505

Active power limitation in %

RW

2

U32

FIX2

0.01

System and device control

Parameter.Inverter.WModCfg.WCnstCfg.WNomPrc

0 .. 100 %

100 %

44507

Type of AC control

RW

3

U32

TAGLIST

-

AC Side

Operation.AcCtrlType

-

-

44509

Switchovers in the redundancy system, acknowledge errors

RW

3

U32

TAGLIST

-

Device

Operation.Rdt.Ackn

-

-

44511

Presetting of Q(V) curve

RW

2

U32

TAGLIST

-

System and device control

Parameter.Inverter.VArModCfg.VArCtlVolCfg.Crv.PreSet

4306: Single Droop
4307: Droop with 4 supporting points and hysteresis
4308: Droop with 6 supporting points
4309: Droop with 8 supporting points
4310: Droop with 10 supporting points
4311: Droop with 12 supporting points
4312: Droop with 14 supporting points

4306: Single Droop

44513

Switchover of the role in the redundancy system

RW

3

U32

TAGLIST

-

Device

Operation.Rdt.Switch

-

-

44515

Manually set active power setpoint in %

RW

2

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCnstCfg.WNomEna

303: Off
308: On

303: Off

44517

Manually set active power setpoint in W

RW

3

U32

TAGLIST

-

System and device control

Inverter.WModCfg.WCnstCfg.WEna

-

-

44519

Frequency containment reserve (FCR), reference active power for active power offset

RW

2

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.WDifRefMod

4354: Maximum active power export
4443: Current power
4444: Potential power

4354: Maximum active power export

44521

Frequency containment reserve (FCR), cut-off point at overfrequency

RW

2

U32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Crv.HzOv[0]

40 .. 70 Hz

50 Hz

44523

Frequency containment reserve (FCR), cut-off point at overfrequency

RW

2

U32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Crv.HzOv[1]

40 .. 70 Hz

50 Hz

44525

Frequency containment reserve (FCR), cut-off point at overfrequency

RW

2

U32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Crv.HzOv[2]

40 .. 70 Hz

50 Hz

44527

Frequency containment reserve (FCR), active power offset per Hz at overfrequency

RW

2

S32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Crv.HzOvGra[0]

-1000 .. 0 %

-50 %

44529

Frequency containment reserve (FCR), active power offset per Hz at overfrequency

RW

2

S32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Crv.HzOvGra[1]

-1000 .. 0 %

-50 %

44531

Frequency containment reserve (FCR), active power offset per Hz at overfrequency

RW

2

S32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Crv.HzOvGra[2]

-1000 .. 0 %

-50 %

44533

Frequency containment reserve (FCR), threshold for activation at overfrequency

RW

2

U32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Crv.DbHzOv

40 .. 70 Hz

50.1 Hz

44535

Frequency containment reserve (FCR), cut-off point at underfrequency

RW

2

U32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Crv.HzUn[0]

40 .. 70 Hz

50 Hz

44537

Frequency containment reserve (FCR), cut-off point at underfrequency

RW

2

U32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Crv.HzUn[1]

40 .. 70 Hz

50 Hz

44539

Frequency containment reserve (FCR), cut-off point at underfrequency

RW

2

U32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Crv.HzUn[2]

40 .. 70 Hz

50 Hz

44541

Frequency containment reserve (FCR), active power offset per Hz at underfrequency

RW

2

S32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Crv.HzUnGra[0]

-1000 .. 0 %

-50 %

44543

Frequency containment reserve (FCR), active power offset per Hz at underfrequency

RW

2

S32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Crv.HzUnGra[1]

-1000 .. 0 %

-50 %

44545

Frequency containment reserve (FCR), active power offset per Hz at underfrequency

RW

2

S32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Crv.HzUnGra[2]

-1000 .. 0 %

-50 %

44547

Frequency containment reserve (FCR), threshold for activation at underfrequency

RW

2

U32

FIX3

0.001

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Crv.DbHzUn

40 .. 70 Hz

49.9 Hz

44549

Frequency containment reserve (FCR), actual value filter for measured frequency value

RW

2

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Dyn.HzFilTmEna

303: Off
308: On

308: On

44551

Frequency containment reserve (FCR), response time of actual value filter for measured frequency value

RW

2

U32

FIX2

0.01

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Dyn.HzFilTms

0.01 .. 5 s

1 s

44553

Frequency containment reserve (FCR), operating reserve related to the available active power

RW

2

U32

FIX2

0.01

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.WResNom

0 .. 100 %

10 %

44555

Frequency containment reserve (FCR), filter for available active power

RW

2

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Dyn.WAvalFilTmEna

303: Off
308: On

303: Off

44557

Frequency containment reserve (FCR), response time of filter for available active power

RW

2

U32

FIX2

0.01

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Dyn.WAvalTms

0.01 .. 3600 s

1 s

44559

Frequency containment reserve (FCR), limitation of ramp rate of available active power

RW

2

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Dyn.WAvalGraEna

303: Off
308: On

308: On

44561

Frequency containment reserve (FCR), ramp-up rate of available active power

RW

2

U32

FIX2

0.01

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Dyn.WAvalGraPos

0.01 .. 10000 %/s

20 %/s

44563

Frequency containment reserve (FCR), ramp-down rate of available active power

RW

2

U32

FIX2

0.01

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Dyn.WAvalGraNeg

0.01 .. 10000 %/s

20 %/s

44565

Frequency containment reserve (FCR), setpoint filter for active power offset

RW

2

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Dyn.WDifFilTmEna

303: Off
308: On

308: On

44567

Frequency containment reserve (FCR), response time of setpoint filter for active power offset

RW

2

U32

FIX2

0.01

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Dyn.WDifFilTms

0.01 .. 3600 s

1 s

44569

Frequency containment reserve (FCR), limitation of ramp rate of active power offset

RW

2

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Dyn.WDifGraEna

303: Off
308: On

303: Off

44571

Frequency containment reserve (FCR), ramp-up rate of active power offset

RW

2

U32

FIX2

0.01

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Dyn.WDifGraPos

0.01 .. 10000 %/s

20 %/s

44573

Frequency containment reserve (FCR), ramp-down rate of active power offset

RW

2

U32

FIX2

0.01

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.Dyn.WDifGraNeg

0.01 .. 10000 %/s

20 %/s

44575

Frequency containment reserve (FCR), base active power

RW

2

U32

TAGLIST

-

System and device control

Parameter.Inverter.WModCfg.WCtlHzFsmCfg.WBaseMod

5014: Current maximum active power setpoint
5015: Minimum from active power setpoints and available power

5014: Current maximum active power setpoint